4.9.2 APC Battery Breaker Box Connection Diagram (120-480kW)

External Connection

UPS

Ampere

Connection

Max.

Dimensions

Weight

 

Rating

Cable

short-

HxWxD [mm]

[kg]

 

[A]

[mm2]

circuit

 

 

 

 

 

current [kA]

 

 

 

 

 

 

 

 

480kW

800

3//150

40

1035x835x300

100

 

 

 

 

 

 

4.9.2 APC Battery Breaker Box Connection Diagram (120-480kW)

Battery 1

Battery 2

UPS Battery 1

UPS Battery 2

Main cables are connected directly

to component terminals

X009 LED signal from UPS “OK to operate corresponding MCCB”

X010 MCCB position signals for UPS

X011 Trip for emergency stop (220-240V AC)

4.9.3 UPS with External Battery in Battery Breaker Box/Fuse-box Configuration

990-4059

30

Installation Guide APC Silcon 480kW 400V UPS

Page 30
Image 30