Options/Accessories

6.6.1 Connecting Isolation Transformer

Isolation

UPS

External

External

External PE

External

External

Transformer

 

Input

Input Cable

Cable

Output

Temp. Signal

 

 

Fuses* FM

[mm2]

[mm2]

Cable

Cable

 

 

[A]

380-415V

 

[mm2]

[mm2]

 

 

380-415V

 

 

 

 

 

 

 

 

 

 

 

540kW

480kVA

1000

3//200

200

3//200

2

 

 

 

 

 

 

 

*DIN gL types

PVC cables insulated to withstand a maximum ambient temperature of 30°C

NOTICE!

If an MCCB is used in stead of external input fuses, the MCCB load capacity must be 8xIn (nominal current) for minimum 10 ms.

NOTICE!

Check correct phase rotation of mains input voltage! Maximum input/output cables: 3//300 mm2. If input neutral is not available, an optional Dzn0 or Dyn11 input isolation transformer must be used.

NOTICE!

All external cable dimensions are recommended sizes only. Refer to local legal regulations.

990-4059

Installation Guide APC Silcon 480kW 400V UPS