External Connection
4.0External Connection
4.1Connecting the UPS
Right side view
Relay board Please refer
to “Relay Board” section
Front view
System Integration
Interface
Communication
Interface
Parallel Controller
| Battery |
| |
| X004:- | X003:+ |
|
| 2 |
| 1 |
X005 | X004:+ | X003:- | X001 |
| 2 |
| 1 |
NOTICE!
Check correct phase rotation of mains input voltage!!
Max. input/output cables: 3//300 mm2.
If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required.
CAUTION!
This UPS unit is an EN
CAUTION!
At a switch mode load of 100% the neutral must be rated for 200% output phase current.
| |
|
|
Installation Guide APC Silcon 480kW 400V UPS | 7 |