Parameter

Programming Parameters

System Configuration Parameters (password protected)

Parameter

Setting*

Comments

 

 

 

Enter System no.

380, 400, 415

Optional selection of voltage

Voltage L-L

 

 

 

 

 

System Frequency

50/60

Optional selection of frequency

 

 

 

Isolation Transformer Input

YES, NO

YES if optional input isolation transformer is available

 

 

 

IsolationTransformer

YES, NO

YES if optional output isolation transformer is available

Output

 

 

 

 

 

Delta Soft Start Time

1, 10, 20, 40 sec.

Input current switching in ramp function. Use higher

 

 

values for smaller/unstable diesel generators

 

 

 

External SSW present

YES, NO

YES for systems with external static bypass switch

 

 

 

Normal Charge Voltage

410-460V

Setting of float charge voltage at 20°C

 

438V

(Automatic compensation for temperature deviations)

 

 

 

Boost Charge Voltage

438-460V

Setting of boost charge voltage at 20°C

 

438V

(Automatic compensation for temperature deviations)

 

 

 

Low Battery warning

336-384V

Discharged Battery warning

 

336V

 

 

 

 

Low Battery shut-down

310-336V

Switches off system at min. permissible battery

 

326V

voltage

 

 

 

Synchronization

0.25, 0.5, 1, 2, 4

Syncronization speed.

 

Hz/sec.

 

 

 

 

High Battery Temperature

15-40°C

Alarm - Ambient temperature for battery too high

 

35°C

 

 

 

 

Common fault delay

0, 10, 20,

Delay before common fault alarm relay is activated

 

30 sec.

 

 

 

 

Reset operation mode lock

YES, NO

YES resets system locked in bypass or battery

 

 

operation mode caused by system failures (only

 

 

applicable for service personnel)

 

 

 

Expected back-up time

0.1-999.9

Expected UPS back-up time in minutes when running

(min.)

5.0

at 100% ohmic load. Time used by ABM**

 

 

 

Battery Capacity in (Ah)

0.1-999.9

Total Battery capacity in Ah.

 

7.0

Setting used by ABM**.

 

 

 

Highest Station Address

2-9

Highest station address in parallel system

 

 

 

Station Address

1-9

Station address in parallel system

 

 

 

APM Mode Active

Disabled

Use only in parallel systems.

(Advanced Power

Redundant +1

Disabled: Advanced power management off.

Management)

Parallel +1

Redundant +1: Redundant operation with one unit

 

 

being inactive in parallel system

 

 

Parallel +1: Redundant operation with all units in

 

 

operation.

 

 

 

APM Test Mode Active

YES, NO

YES, if APM test mode is active

 

 

 

Battery Connection

Common,

Common: if common battery is used in parallel system.

 

Separate

Separate: if separate battery is used

 

 

 

*Bold text refers to factory standard setting **Advanced Battery Monitor