External Connection

UPS

External

External

External PE

Maximum

External

 

Input

Input Cable

Cable

External

Output Cable

 

Fuses* FM

[mm2]

[mm2]

Output

[mm2]

 

[A]

380-415V

 

Fuses*

 

 

380-415V

 

 

[A]

 

 

 

 

 

 

 

480kW

1000

3//200

200

800

3//150

 

 

 

 

 

 

* DIN gL types

NOTICE!

All cable dimensions are recommended sizes only.

Refer to local legal regulations.

UPS

External Alarm

External System

External Battery

External Battery

 

Cable max.

Earth Cable

Breaker

Cable [mm2]

 

[mm2]

[mm2]**

[A]

 

 

 

 

 

 

480kW

2

30

800

3//150

 

 

 

 

 

PVC cables insulated to withstand ambient temperature of max. 30°C

** Must be rated as external PE cable if mains system is not supplying PE

NOTICE!

Install gland plate in bottom of unit.

4.2System Integration Interface

990-4059

8

Installation Guide APC Silcon 480kW 400V UPS

Page 8
Image 8
American Power Conversion 480kW 400V manual System Integration Interface