American Power Conversion 480kW 400V manual Programming Parameters

Models: 480kW 400V

1 72
Download 72 pages 33.09 Kb
Page 32
Image 32
Programming Parameters

Programming Parameters

5.0 Programming Parameters

Below table shows operating parameters programmable from keyboard. Only qualified users should re-set programming parameters.

5.1Parameters

Parameter

Setting*

Comments

 

 

 

 

 

 

 

 

 

 

Bypass operation

YES, NO

YES will switch the system into bypass mode

 

 

 

 

 

 

 

 

 

GB, D, F

 

 

 

 

 

 

Language

DK, S, SF

Language of text in display

NL, PL, CZ

 

 

 

 

 

 

 

 

E, P, SK, H

 

 

 

 

 

 

 

 

 

 

 

 

Autostart

YES, NO

Automatic restart by mains return

(1 min.delay). Ensures quick battery recharge

 

 

 

 

 

 

 

 

Remote shutdown active

YES, NO

Shutdown of UPS by remote signal when in

battery operation. Saves battery energy

 

 

 

 

 

 

 

 

Remote shutdown

HIGH, LOW

Nature of remote shutdown signal level

 

 

 

 

 

 

 

 

 

0, 1, 2, 3, 4

 

 

 

 

 

 

Remote shutdown time

5, 6, 7, 8, 9

Time delay on remote shutdown of UPS

 

10 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Initiates back-up time check.

Battery capacity test

---

Time measured from start until it reaches low

DC warning level.

 

 

 

 

 

 

(See User Guide section 6 )

 

 

 

 

 

 

Battery monitor test**

---

Initiates checks of battery condition by 25%

discharging

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic battery test**

OFF, 3, 6 months

Activates the battery monitor test in cyclic

intervals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery monitor reset**

---

Press the

 

and

 

 

key

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to resets alarm (flashing light)!

 

 

 

 

 

 

 

 

Boost charge

YES, NO

YES results in boost charge (10 hours)

 

 

 

 

 

 

Autoboost charge

YES, NO

YES results in boost charge after battery

operation. (10 hours)

 

 

 

 

 

 

 

 

 

 

 

Enter new date

YYMMDD

Set tolocal date

 

 

 

 

 

 

 

Enter new time

HHMMSS

Set to local time (24 hour clock)

 

 

 

 

 

 

 

 

*Factory settings in bold

**Only for systems with Battery Monitor active

***Do not leave system running in bypass mode (Static bypass) for extended periodes of time, as batteries are not recharged in bypass mode.