Carrier 50PG03-16 installation instructions 50PG03−16, 208A00

Models: 50PG03-16

1 32
Download 32 pages 23.54 Kb
Page 23
Image 23
Manual background

Table 2 — Electrical Data — Units With Optional Powered Convenience Outlet (cont)

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

 

 

ELECTRIC HEAT

POWER SUPPLY

 

DISCONNECT SIZE

 

 

 

 

 

 

POWER

 

CRSINGLE

 

 

RANGE

 

(EA)

 

 

 

UNIT

POWER

 

OFM

IFM

IFM

 

 

 

 

WIRING

 

 

 

 

 

 

 

 

 

 

EXHAUST

 

 

 

PART NO.

 

50PG

SUPPLY

 

 

 

FLA

FLA

TYPE

CRHEATER

NOMINAL

 

 

FIG. NO.

MIN MAX

RLA

LRA

FLA

MOCP†

(NOTE3)

FLA

 

 

 

 

 

FLA

MCA

LRA

 

VOLTS-PH-HZ

 

 

 

 

 

 

 

PART NO.

KW*

 

 

 

 

 

 

 

 

 

 

 

 

208A00

 

 

 

 

 

 

4.9

Low

209A00

 

 

 

 

 

 

210A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

211A00

 

208/230-3-60

187

253

14.6

0.9

1.4

212A00

 

 

(cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208A00

 

 

 

 

 

 

5.2

High

209A00

 

 

 

 

 

 

210A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

211A00

 

 

 

 

 

 

 

 

212A00

 

 

 

 

 

 

 

 

215A00

 

 

 

 

 

 

2.1

Low

216A00

 

 

 

 

 

 

217A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

218A00

 

 

 

 

 

 

 

 

219A00

 

 

 

 

 

 

 

 

215A00

 

 

 

 

 

 

2.6

High

216A00

 

 

 

 

 

 

217A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

218A00

 

460-3-60

414

506

 

0.5

 

219A00

 

 

 

 

05

 

 

 

 

 

 

 

215A00

(cont)

 

 

 

 

 

2.1

Low

216A00

 

 

 

 

 

 

217A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

218A00

 

 

 

 

 

 

 

0.6

219A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

215A00

 

 

 

 

 

 

2.6

High

216A00

 

 

 

 

 

 

217A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

218A00

 

 

 

 

 

 

 

 

219A00

 

 

 

 

 

 

 

Low

221A00

 

 

 

 

 

 

 

222A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

223A00

 

 

 

 

 

 

 

High

221A00

 

 

 

 

 

 

 

222A00

 

 

 

 

 

 

 

 

 

575-3-60

518

632

34.0

0.4 2.0

 

223A00

 

 

 

 

 

 

 

 

 

 

Low

221A00

 

 

 

 

 

 

 

222A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.4

223A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

221A00

 

 

 

 

 

 

 

222A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

223A00

 

 

 

 

 

 

 

 

201A00

 

 

 

 

 

 

 

 

202A00

 

 

 

 

 

 

4.9

Low

203A00

 

 

 

 

 

 

 

 

204A00

 

 

 

 

 

 

 

 

205A00

06

208/230-1-60

187

253

26.9 145

1.5

 

206A00

 

 

 

 

 

 

 

 

 

 

201A00

 

 

 

 

 

 

 

 

202A00

 

 

 

 

 

 

7.0

High

203A00

 

 

 

 

 

 

 

 

204A00

 

 

 

 

 

 

 

 

205A00

 

 

 

 

 

 

 

 

206A00

 

 

LEGEND

 

 

 

 

 

 

FLA

Full Load Amps

 

 

 

 

 

HACR −

Heating, Air Conditioning and Refrigeration

 

 

IFM

Indoor − Fan Motor

 

 

 

 

LRA

Locked Rotor Amps

 

 

 

 

MCA

Minimum Circuit Amps

 

 

 

 

MOCP −

Maximum Overcurrent Protection

 

 

 

NEC

National Electrical Code

 

 

 

OFM

Outdoor−Fan Motor

 

 

 

 

RLA

− Rated Load Amps

 

 

 

 

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu- tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equip- ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.

max voltage deviation from average voltage

% Voltage Imbalance

= 100 x

average voltage

 

 

30.2/30.2

40/40

 

31/31

111/111

 

10.0/11.5

 

30.2/30.2

40/40

030A00

31/31

111/111

15

15.0/17.3

 

32.6/35.0

40/40

030A00

31/33

111/111

15

20.0/23.1

 

38.9/42.2

40/45

030A00

36/39

111/111

15

30.0/34.6

11.3/15.0

51.4/56.6

60/60

030A00

47/53

111/111

15

40.0/46.2

15.0/20.0

63.9/71.0

70/80

031A00

59/66

111/111

16

 

 

30.5/30.5

45/45

 

31/31

130/130

 

10.0/11.5

 

30.5/30.5

45/45

030A00

31/31

130/130

15

15.0/17.3

 

33.0/35.3

45/45

030A00

31/33

130/130

15

20.0/23.1

 

39.3/42.6

45/45

030A00

36/40

130/130

15

30.0/34.6

11.3/15.0

51.8/57.0

60/60

030A00

48/53

130/130

15

40.0/46.2

15.0/20.0

64.3/71.4

70/80

031A00

59/66

130/130

16

 

 

13.6

20

 

14

55

 

 

 

13.6

20

030A00

14

55

15

 

 

16.2

20

030A00

15

55

15

11.5

10.0

19.8

20

030A00

18

55

15

17.3

15.0

27.0

30

030A00

25

55

15

23.1

20.0

34.2

35

030A00

31

55

15

 

 

14.1

20

 

14

64

 

 

 

14.1

20

030A00

14

64

15

 

 

16.8

20

030A00

15

64

15

11.5

10.0

20.4

25

030A00

19

64

15

17.3

15.0

27.6

30

030A00

25

64

15

23.1

20.0

34.8

35

030A00

32

64

15

 

 

14.2

20

 

14

56

 

 

 

14.2

20

030A00

14

56

15

 

 

16.9

20

030A00

16

56

15

11.5

10.0

20.5

25

030A00

19

56

15

17.3

15.0

27.7

30

030A00

26

56

15

23.1

20.0

35.0

40

030A00

32

56

15

 

 

14.7

20

 

15

65

 

 

 

14.7

20

030A00

15

65

15

 

 

17.5

20

030A00

16

65

15

11.5

10.0

21.2

25

030A00

19

65

15

17.3

15.0

28.4

30

030A00

26

65

15

23.1

20.0

35.6

40

030A00

33

65

15

 

 

10.7

15

 

11

42

 

 

10.0

16.3

20

030A00

15

42

15

13.9

15.0

22.1

25

030A00

20

42

15

18.5

20.0

27.9

30

030A00

26

42

15

 

 

10.6

15

 

11

48

 

 

10.0

16.1

20

030A00

15

48

15

13.9

15.0

22.0

25

030A00

20

48

15

18.5

20.0

27.8

30

030A00

26

48

15

 

 

12.1

15

 

12

44

 

 

10.0

18.0

20

030A00

17

44

15

13.9

15.0

23.9

25

030A00

22

44

15

18.5

20.0

29.6

30

030A00

27

44

15

 

 

12.0

15

 

12

50

 

 

10.0

17.9

20

030A00

16

50

15

13.9

15.0

23.8

25

030A00

22

50

15

18.5

20.0

29.5

30

030A00

27

50

15

 

 

 

 

 

 

164/164

 

17.3/

 

 

 

028A00

 

164/164

13

26.0/

 

 

 

028A00

 

164/164

13

34.7/

 

 

 

028A00

 

164/164

13

52.0/

11.3/15.0

 

 

029A00

 

164/164

14

69.3/

15.0/20.0

 

100/125

029A00

 

164/164

14

86.7/100.0

18.8/25.0

119.4/136.1

125/150

029A00

111/126

164/164

14

 

 

 

 

 

 

190/190

 

17.3/

 

 

 

028A00

 

190/190

13

26.0/

 

 

 

028A00

 

190/190

13

34.7/

 

 

 

028A00

 

190/190

13

52.0/

11.3/15.0

 

 

029A00

 

190/190

14

69.3/

15.0/20.0

100.4/113.8

110/125

029A00

 

190/190

14

86.7/100.0

18.8/25.0

122.1/138.8

125/150

029A00

113/129

190/190

14

Example: Supply voltage is 460-3-60

 

 

 

 

AB = 224 v

 

BC = 231 v

 

AC = 226 v

224 + 231 + 226

Average Voltage =

3

 

=681

3

=227

Determine maximum deviation from average voltage.

Maximum deviation is 4 v.

Determine percent of voltage imbalance.

4

% Voltage Imbalance

= 100 x

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

3.Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if field−supplied pressure connectors are used.

50PG03−16

23

Page 23
Image 23
Carrier 50PG03-16 installation instructions 50PG03−16, 208A00