Table 19 — C Control Current LED Status

and Alarm Relay Operations

LED STATUS

 

DESCRIPTION OF OPERATION

ALARM RELAY

 

 

 

 

Normal Mode

Open

 

On

 

Normal Mode with

Cycle

 

 

 

 

PM Warning

(closed 5 sec.,

 

 

 

 

Open 25 sec.)

 

 

 

 

 

 

Off

 

C Control is non-functional

Open

Slow Flash

 

Fault Retry

Open

 

Fast Flash

 

Lockout

Closed

Slow Flash

 

 

Open

 

Over/Under Voltage Shutdown

(Closed after

 

 

 

 

 

15 minutes)

Flashing Code 1

Test Mode — No fault in memory

Cycling Code 1

Flashing Code 2

Test Mode — HP Fault in memory

Cycling Code 2

Flashing Code 3

Test Mode — LP Fault in memory

Cycling Code 3

Flashing Code 4

Test Mode — FP1 Fault in memory

Cycling Code 4

Flashing Code 5

Test Mode — FP2 Fault in memory

Cycling Code 5

Flashing Code 6

Test Mode — CO Fault in memory

Cycling Code 6

Flashing Code 7

 

Test Mode — Over/Under

Cycling Code 7

 

shutdown in memory

 

 

 

 

 

Flashing Code 8

 

Test Mode — PM in memory

Cycling Code 8

Flashing Code 9

 

Test Mode — Test Mode — FP1/

Cycling Code 9

 

FP2 Swapped Fault in memory

 

 

 

 

 

 

LEGEND

 

 

CO

Condensate Overflow

 

FP

Freeze Protection

 

HP

High Pressure

 

LED — Light-Emitting Diode

 

LP

Low Pressure

 

PM

Performance Monitor

 

NOTES:

1.Slow flash is 1 flash every 2 seconds.

2.Fast flash is 2 flashes every 1 second.

3.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat continually until the fault is cleared.

Table 20 — C Control LED Code and

Fault Descriptions

 

LED

FAULT

DESCRIPTION

CODE

 

 

 

1

No fault in memory

There has been no fault since

 

 

 

the last power-down to power-up

 

 

 

sequence

 

2

High-Pressure Switch

HP Open Instantly

 

3

Low-Pressure Switch

LP open for 30 continuous sec-

 

 

 

onds before or during a call

 

 

 

(bypassed for first 60 seconds)

 

4

Freeze Protection Coax

FP1 below Temp limit for 30 con-

 

 

— FP1

tinuous seconds (bypassed for

 

 

 

first 60 seconds of operation)

 

5

Freeze Protection Air Coil

FP2 below Temp limit for 30 con-

 

 

— FP2

tinuous seconds (bypassed for

 

 

 

first 60 seconds of operation)

 

6

Condensate overflow

Sense overflow (grounded) for

 

 

 

30 continuous seconds

 

7

Over/Under Voltage

"R" power supply is <19VAC or

(Autoreset)

Shutdown

>30VAC

 

8

PM Warning

Performance Monitor Warning

 

 

 

has occurred.

 

9

FP1 and FP2 Thermistors

FP1 temperature is higher than

 

 

are Swapped

FP2 in heating/test mode, or FP2

 

 

 

temperature is higher than FP1

 

 

 

in cooling/test mode.

 

LEGEND

 

FP

Freeze Protection

 

HP

High Pressure

 

LED — Light-Emitting Diode

 

LP

Low Pressure

 

PM

Performance Monitor

 

Retry Mode — In Retry mode, the status LED will start to flash slowly to signal that the control is trying to recover from an input fault. The control will stage off the outputs and try to

again satisfy the thermostat used to terminal Y. Once the ther- mostat input calls are satisfied, the control will continue normal operation.

NOTE: If 3 consecutive faults occur without satisfying the thermostat input call to terminal Y, the control will go into lockout mode. The last fault causing the lockout is stored in memory and can be viewed by entering Test mode.

Aquazone™ Deluxe D Control LED Indica- tors — There are 3 LED indicators on the D Control:

STATUS LED — Status LED indicates the current status or mode of the D control. The Status LED light is green.

TEST LED — Test LED will be activated any time the D control is in test mode. The Test LED light is yellow.

FAULT LED — Fault LED light is red. The fault LED will always flash a code representing the last fault in memory. If there is no fault in memory, the fault LED will flash code 1 on and appear as 1 fast flash alternating with a 10-second pause. See Table 21.

SERVICE

Perform the procedures outlined below periodically, as indicated.

IMPORTANT: When a compressor is removed from this unit, system refrigerant circuit oil will remain in the com- pressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.

IMPORTANT: All refrigerant discharged from this unit must be recovered without exception. Technicians must fol- low industry accepted guidelines and all local, state and fed- eral statutes for the recovery and disposal of refrigerants.

IMPORTANT: To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must only be serviced by technicians which meet local, state and federal proficiency requirements.

IMPORTANT: To prevent injury or death due to electrical shock or contact with moving parts, open unit disconnect switch before servicing unit.

Filters — Filters must be clean for maximum performance. Inspect filters every month under normal operating conditions. replace when necessary.

IMPORTANT: Units should never be operated with- out a filter.

Water Coil — Keep all air out of the water coil. Check open loop systems to be sure the well head is not allowing air to infiltrate the water line. Always keep lines airtight.

Inspect heat exchangers regularly, and clean more frequent- ly if the unit is located in a “dirty” environment. The heat exchanger should be kept full of water at all times. Open loop systems should have an inverted P trap placed in the discharge line to keep water in the heat exchanger during off cycles. Closed loop systems must have a minimum of 15 PSI during the summer and 40 PSI during the winter.

Check P trap frequently for proper operation.

20

Page 20
Image 20
Carrier 50RTG Service, Control Current LED Status Alarm Relay Operations, Control LED Code Fault Descriptions

50RTG specifications

The Carrier 50RTG represents a significant advancement in the field of rooftop air conditioning systems, combining performance, efficiency, and reliability for commercial applications. Designed to meet the rigorous demands of today’s buildings, the 50RTG series is ideally suited for a variety of environments, including retail, office spaces, and industrial facilities.

One of the standout features of the Carrier 50RTG is its energy efficiency. Utilizing the latest in compressor technology, these units achieve high Seasonal Energy Efficiency Ratios (SEER) and Energy Efficiency Ratios (EER), which translates to lower energy costs for users. This efficiency is further enhanced by the incorporation of environmentally friendly refrigerants that comply with current regulations, reducing the overall carbon footprint of the unit.

Another notable characteristic of the 50RTG series is its modular design. The unit can be tailored to specific requirements, making it versatile for different installation scenarios. This modularity not only simplifies maintenance and repair operations but also allows for easy upgrades as technologies evolve or as space demands change.

The advanced control system in the 50RTG is another key technology that sets it apart from competing products. Intuitive user interfaces and smart controls enable precise temperature regulation and improved energy management. These controls often include features such as variable speed fans and integrated economizers, which optimize the system's performance in real-time based on current load requirements.

Durability is also a hallmark of the Carrier 50RTG. Constructed with robust materials and designed to withstand harsh weather conditions, these units provide dependable operation year-round. The corrosion-resistant finish and weather-tight construction ensure that the systems maintain their performance levels and aesthetic appeal over time.

Additionally, the 50RTG series is designed with a focus on low noise operation. With quieter components and advanced noise control technology, these units are ideal for noise-sensitive environments, ensuring that occupants can work, live, or shop in comfort without disruptive background noise.

In summary, the Carrier 50RTG series exemplifies the perfect combination of energy efficiency, advanced technology, customization potential, durability, and low noise operation, making it a top choice for commercial heating and cooling needs. Its innovative features and reliable performance solidify its status as a leader in rooftop HVAC solutions, catering to the evolving requirements of modern buildings.