Carrier 50VL---A SPECIAL PROCEDURES FOR 208-VOPERATION, Control Voltage Connections, 50VL--A

Models: 50VL---A

1 30
Download 30 pages 32.33 Kb
Page 10
Image 10
SPECIAL PROCEDURES FOR 208-V OPERATION

50VL-- A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPECIAL PROCEDURES FOR 208-V OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(SEE UNIT WIRING

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

WARNING

 

 

HIGH VOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

!

 

 

 

 

POWER LEADS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LABEL)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-PHASE SHOWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL SHOCK HAZARD

 

 

 

1-PHASE USES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Failure to follow this warning could result in personal

 

 

 

TWO POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EQUIP GR

 

 

 

 

 

 

 

 

 

 

 

injury or death.

 

 

 

 

LEADS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIELD-SUPPLIED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Before installing or servicing system, always turn off main

 

 

 

 

 

 

 

 

 

 

 

FUSED DISCONNECT

 

 

 

 

CONTROL BOX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power to system and install lockout tag. With disconnect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

switch open, move black wire from transformer (3/16

 

 

 

 

 

 

 

 

 

 

 

WHT(W1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W1

 

 

 

in.)(4.8 mm) terminal marked 230 to terminal marked 208.

 

 

 

 

 

 

 

 

 

 

 

VIO (W2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W2

 

 

 

This retaps transformer to primary voltage of 208 vac.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YEL(Y)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW-VOLTAGE

 

 

 

 

 

 

 

GRN(G)

 

 

G

 

 

CONTROL VOLTAGE CONNECTIONS

 

 

 

 

 

 

 

RED(R)

 

 

 

 

 

THERMOSTAT NOTE: Do not use any type of power-stealing thermostat. Unit

 

 

 

 

 

 

 

 

 

 

 

POWER LEADS

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

(SEE UNIT

 

 

 

 

 

 

 

BRN(C)

 

 

 

(TYPICAL)

control problems may result.

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRING LABEL)

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

Use no. 18 American Wire Gage (AWG) color-coded, insulated

 

 

 

 

 

 

 

 

 

BLU (DH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DH

 

 

(35°C minimum) wires to make the control voltage connections

 

 

 

 

 

 

 

 

 

GRA (Y2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-Phase

 

 

between the thermostat and the unit. If the thermostat is located

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Only

 

 

more than 100 ft (30.5 m) from the unit (as measured along the

 

 

SPLICE BOX

 

 

 

 

 

 

 

 

 

 

control voltage wires), use no. 16 AWG color-coded, insulated

 

 

 

 

 

 

 

 

 

 

 

 

(35° C minimum) wires.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A09066

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STANDARD CONNECTION

 

Fig. 10 - High- and Control-Voltage Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Locate the seven (eight for 3-phase) low voltage thermostat leads

 

5. Connect field wire L2 to yellow wire on connection 23 of

in 24 volt splice box. A gray wire is standard on 3-phase units for

 

the compressor contactor.

 

 

 

 

 

 

 

 

 

 

connection to an economizer. See Fig. 10 for connection diagram.

Three-phase units:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Run the low-voltage leads from the thermostat, through the control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wiring inlet hole grommet (Fig. 2 and 3), and into the low-voltage

 

1. Run the high-voltage (L1, L2, L3) and ground lead into the

 

splice box. Provide a drip loop before running wires through panel.

 

control box.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Secure and strain relief all wires so that they do not interfere with

 

2. Connect ground lead to chassis ground connection.

 

 

 

operation of unit.

 

 

 

 

3. Locate the black and yellow wires connected to the line side

 

 

 

 

If an accessory electric heater is installed, low voltage leads from

 

of the contactor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heater must be connected to factory supplied control leads from

 

4. Connect field L1 to black wire on connection 11 of the

 

Indoor Fan Board P4 connector.

 

compressor contactor.

 

 

 

 

 

 

 

 

 

 

NOTE: If the unit 24V wires do not have a matching receptacle,

 

5. Connect field wire L3 to yellow wire on connection 13 of

 

cut the 24V wires from the electric heater plug, strip the ends, and

 

the compressor contactor.

 

 

 

 

 

 

 

 

 

 

wire nut together to match the schematic connections. If the electric

 

6. Connect field wire L2 to blue wire from compressor.

heater 24V wires do not have a matching plug, cut the 24V wires

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from the unit receptacle, strip the ends, and wire nut together to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

match the schematic connections.

Factory wires are provided for electric heat staging W1 and W2 (W2 and W3 on IFB). If room thermostat has only one stage of supplemental heat, connect white and violet wires shown in Fig. 10 to second stage heat field wire.

Some electric heaters have four control wires (plus common wire). Consult unit wiring diagram and electric heater wiring diagram for additional details.

TRANSFORMER PROTECTION

The transformer is of the energy-limiting type, however a direct short will likely blow a secondary fuse. If an overload or short is present, correct overload condition and check for blower fuse on Indoor Fan Board. Replace fuse as required with correct size and rating.

10

Page 10
Image 10
Carrier 50VL---A SPECIAL PROCEDURES FOR 208-VOPERATION, Control Voltage Connections, Standard Connection, 50VL--A