Carrier 50VL---A Continuous Fan Operation, Cooling Sequence Of Operation, Interface Fan Board IFB

Models: 50VL---A

1 30
Download 30 pages 32.33 Kb
Page 14
Image 14
Fig. 11 - Interface Fan Board (IFB)

50VL-- A

 

 

 

HIGH

 

STD DEHUM

 

 

 

LOW

COM

 

 

 

 

QC5

 

 

 

 

QC4

QC3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KZ

 

 

 

 

 

 

KL

QCR

 

 

 

 

 

 

 

 

 

 

 

 

 

DCR

 

 

 

 

 

R13

C8

R11

Q1

 

 

C

CDM/C

07

09

0L0

08

 

 

 

 

ALO

 

 

D2

 

 

 

 

 

 

 

 

 

 

 

 

 

QC1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q3

 

 

AL2

24VAC/R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C9

C4

 

 

 

 

 

 

 

G1

RL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G2

 

3AMP

QIL

Z2

06

04

 

 

 

 

 

 

 

 

 

 

 

A7

R9

AB

A15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C0

F1

 

 

 

 

 

 

 

 

U1

 

 

Z1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C3

 

 

R4

RL4

D5

D3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JWZ

 

P3

 

 

R2

JW5

 

R3

R5

R6

 

 

 

 

 

 

 

 

 

 

 

P2

JW3

 

 

 

 

 

 

 

QCB

 

 

 

 

 

P4

 

 

 

 

 

 

 

 

 

 

 

 

SDL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

R

W2 Y

 

C

 

 

W3 W3 W2 W2 C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW4

 

 

 

SSTZ-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1

 

 

Y2

 

Y1

 

 

 

 

 

 

 

 

 

W3 W2

G

C

R

 

 

 

 

 

 

 

DH

Y

 

 

A09059

Fig. 11 - Interface Fan Board (IFB)

SINGLE SPEED COOLING WITH HIGHER ELECTRIC HEAT SPEED

This unit can also be configured to operate with single speed cooling and a higher speed for an accessory electric heater.

1.Using Fig. 11, move the two pin DEHUM jumper from the “STD” position to the “DEHUM” position.

2.See Table 2 for minimum airflow for electric heat operation. Add electric heater and filter pressure drop to duct system static pressure to determine total external static pressure.

3.Select speed tap from Table 4 that will achieve required airflow from Table 2.

4.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 3 for color coding).

5.Connect the desired speed tap wire to the “HIGH” terminal on the interface fan board (IFB).

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit component damage or improper operation.

To use this mode, a speed connection must be made on the “HIGH” terminal that meets or exceeds the minimum airflow found in Table 2.

Table 3 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med--High Speed

Red = Med Speed

Pink = Med--Low Speed

Blue = Low Speed

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect electrical power to the unit and install lockout tag before changing blower speed.

CONTINUOUS FAN OPERATION

When the DEHUM feature is not used, the continuous fan speed will be the same as cooling fan speed. When the DEHUM feature is used, the continuous fan will operate on IFB “LOW” speed when the DH control lead is not energized, or IFB “HIGH” speed when the DH lead is energized (see Fig. 11).

COOLING SEQUENCE OF OPERATION

With the room thermostat SYSTEM switch in the COOL position and the FAN switch in the AUTO position, the cooling sequence of operation is as follows:

When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and time delay relay (TDR) (through unit wire G) across the 24-V secondary of transformer (TRAN).

The normally open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to condenser (outdoor) fan motor (OFM). Both motors start instantly.

A set of normally open contacts on the interface fan board (IFB) are closed which energizes a circuit to the indoor fan motor (IFB).

NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed.

The cooling cycle remains on until the room temperature drops to a point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat breaks the circuit between thermostat terminal R to terminals Y and G. These open circuits deenergize contactor coil C and IFB. The condenser and compressor motors stop. After a 90-second delay, the blower motor stops. The unit is in a standby condition, waiting for the next call for cooling from the room thermostat.

14

Page 14
Image 14
Carrier 50VL---A Continuous Fan Operation, Cooling Sequence Of Operation, Interface Fan Board IFB, 50VL--A