Carrier 50VL---A Install Electrical Connections, High-Voltageconnections, 50VL--A

Models: 50VL---A

1 30
Download 30 pages 32.33 Kb
Page 9
Image 9
Fig. 9 - Supply and Return Duct Opening

Horizontal Duct Covers

A09076

Basepan

 

Downflow

 

(Vertical)

Basepan

Supply

Downflow

Knockout

(Vertical)

 

 

Return

 

Knockout

 

A09093

Fig. 9 - Supply and Return Duct Opening

Step 8 — Install Electrical Connections

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NFPA 70 (NEC) (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.

!CAUTION

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to the unit being installed.

1.Make all electrical connections in accordance with NFPA 70 (NEC) (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.

2.Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.

3.Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate. On 3-phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.

4.Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.

HIGH-VOLTAGE CONNECTIONS

The unit must have a separate electrical service with a field-supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.

The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used. See Fig. 2 and 3 for acceptable location.

See unit wiring label (Fig. 12, 13 and 14) and Fig. 10 for reference when making high voltage connections. Proceed as follows to complete the high-voltage connections to the unit.

Single phase units:

1.Run the high-voltage (L1, L2) and ground lead into the control box.

2.Connect ground lead to chassis ground connection.

3.Locate the black and yellow wires connected to the line side of the contactor.

4.Connect field L1 to black wire on connection 11 of the compressor contactor.

9

50VL-- A

Page 9
Image 9
Carrier 50VL---A Install Electrical Connections, High-Voltageconnections, Supply and Return Duct Opening, 50VL--A