Step 3 — Provide Clearances

The required minimum service clearances are shown in Fig. 2 and

3.Adequate ventilation and outdoor air must be provided. The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. (1219 mm) above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in. (1219 mm) IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor-air inlet or the fan discharge may be detrimental to compressor life.

Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab-mounted units should be at least 4 in. (102 mm) above the highest expected water and runoff levels. Do not use unit if it has been under water.

Step 4 — Field-Fabricate Ductwork

Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, unit is provided with flanges on the horizontal openings. All ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes. See unit rating plate for any required clearances around ductwork. Cabinet return-air static shall not exceed -.25 IN. W.C.

Step 5 — Rig and Place Unit

Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.).

Only trained, qualified crane operators and ground support staff should handle and install this equipment.

When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply.

Training for operators of the lifting equipment should include, but not be limited to, the following:

1.Application of the lifter to the load, and adjustment of the lifts to adapt to various sizes or kinds of loads.

2.Instruction in any special operation or precaution.

3.Condition of the load as it relates to operation of the lifting kit, such as balance, temperature, etc.

Follow all applicable safety codes. Wear safety shoes and work gloves.

A

C

MAXIMUM ALLOWABLE

BDIFFERENCE in. (mm)

 

A-B

B-C

 

A-C

1/4

(6.35)

1/4

(6.35)

1/4

(6.35)

 

 

 

 

 

 

A07925

Fig. 6 - Unit Leveling Tolerances

INSPECTION

Prior to initial use, and at monthly intervals, all rigging shackles, clevis pins, and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Materials showing any kind of wear in these areas must not be used and should be discarded.

!WARNING

UNIT FALLING HAZARD

Failure to follow this warning could result in personal injury or death.

Never stand beneath rigged units or lift over people.

1.Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damaging the unit. If the skid is not available, use a spreader bar of sufficient length to protect the unit from damage.

!WARNING

PROPERTY DAMAGE HAZARD

Failure to follow this warning could result in personal

When straps are taut, the clevis should be a minimum of 36 in. (914 mm) above the unit top cover.

Rigging/Lifting of Unit (See Fig. 5)

!WARNING

UNIT FALLING HAZARD

Failure to follow this warning could result in personal injury or death.

Large base units must be secured to common curb before allowing full weight of unit to rest on curb. Install screws through curb into unit base rails while rigging crane is still supporting unit.

Lifting holes are provided in base rails as shown.

1.Attach shackles, clevis pins, and straps to the base rails of the unit. Be sure materials are rated to hold the weight of the unit (See Fig. 5).

2.Attach a clevis of sufficient strength in the middle of the straps. Adjust the clevis location to ensure unit is lifted level with the ground.

After the unit is placed on the roof curb or mounting pad, remove the top skid.

OPTIONAL

OPTIONAL

RETURN

SUPPLY

AIR

AIR

OPENING

OPENING

 

(50.8mm)

 

EVAP. COIL

COND. COIL

A07926

Fig. 7 - Slab Mounting Detail

50VL-- A

7

Page 7
Image 7
Carrier 50VL---A installation instructions Provide Clearances, Field-Fabricate Ductwork, Rig and Place Unit, Inspection

50VL---A specifications

The Carrier 50VL---A is a powerhouse in the field of air conditioning and heating solutions, designed for residential and commercial applications. This unit exemplifies Carrier’s commitment to efficiency, reliability, and advanced technology. One of the standout features of the 50VL---A is its superior energy efficiency, which is reflected in its high Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF) ratings. These ratings ensure reduced energy consumption and lower utility bills, making it an environmentally friendly choice.

The 50VL---A is designed with a robust scroll compressor that not only enhances performance but also minimizes noise levels during operation. This compressor is integral to the system’s ability to maintain a consistent temperature and humidity level within the space. The unit’s sound-dampening features contribute to a quieter environment, which is particularly important in residential settings.

One of the key technologies integrated into the Carrier 50VL---A is the advanced microprocessor control system. This technology allows for precise temperature adjustments and operational diagnostics, making maintenance easier and more efficient. This system ensures that the unit operates at optimal performance, adapting to changing environmental conditions with ease.

Moreover, the 50VL---A is equipped with a multi-speed blower motor that provides enhanced airflow and comfort. This feature allows users to select different cooling or heating levels according to their specific requirements, promoting customized comfort throughout the home or office.

In addition to its performance capabilities, the Carrier 50VL---A is also built with longevity and durability in mind. The cabinet is constructed from high-quality materials that offer resistance to corrosion and wear, ensuring the unit can withstand various weather conditions over time. Furthermore, the unit’s maintenance-friendly design allows for easy access to key components, simplifying servicing and prolonging the life of the system.

Overall, the Carrier 50VL---A stands out as a reliable and advanced solution for climate control. With its energy-efficient operation, quiet performance, and user-friendly features, it represents a significant investment in home comfort and efficiency. Whether for heating during the colder months or cooling in the summer, the 50VL---A delivers exceptional performance, making it a popular choice among users seeking quality HVAC solutions.