- M U F F L E R S

MUFFLERS -

COMPRESSORSCOMPRESSORS

Fig. 9 - Thermistor Locations

Step 4 - Check Thermistors That Control EXV - Check thermistors that control processor output voltage pulses to EXVs. Circuit A thermistors are T5 and T7. Circuit B thermistors are T6 and T8. Refer to Fig. 9 for location.

1.lJse the temperature subfunction of the status function (pp=]) to determine if thermistors are reading

correctly.

2.Check thermistor calibration at known temperature by measuring actual resistance and comparing value measured with values listed in Table 8.

3.Make sure that thermistor leads are connected to proper pin terminals at 157 terminal strip on processor module and that thermistor probes are located in proper position in refrigerant circuit (Fig. 9).

When above checks have been completed, actual operation of EXV can be checked by using procedures outlined in Step 5.

Step 5 ~ Check Operation of the EXV ~ Use following procedure to check actual operation ofelectronic expan- sion valves.

I. Close liquid line service valve for circut to be checked

and run through the Quick Test step (in subfunction 3 of test function) for the lead compressor in that circuit to pump down the low side of the system.

Repeat test step 3 times to ensure that all refrigerant has been pumped from low side.

NOTE: Be sure to allow compressors to run full 10 seconds at each step.

2.Turn OFF compressor circuit breaker(s). Close com- pressor service valves and vent any remaining refrig- erant from low side of system.

3.Remove screws holding top cover of EXV. Carefully remove top cover, using caution to avoid damage to

the motor leads. If EXV plug was disconnected during

,:’

this process, reconnect it after the cover is removed.

‘:

4. Enter appropriate EXV Quick Test step for EVXA or

 

EXVB in the outputs subfunction of the test function

 

(pq-p-j,.

Press ENTR to initiate test. With cover

 

lifted off the EXV valve body, observe operation of valve motor and lead screw. The motor should turn in the clockwise direction and the lead screw should move down into the motor hub until the valve is fully closed or fully open depending on whether you initiate the open or close test step for that valve. Lead screw movement should be smooth and uniform from fully open to fully closed position, or from fully closed to fully open.

If valve is properly connected to processor and receiv- ing correct signals, yet does not operate as described above, the valve shouId be replaced.

The operation of the EXV valve can also be checked without removing the top cover. This method depends on the operator’s skill in determining whether or not the valve is moving, To use this method, initiate the Quick Test to open the valve. Immediately grasp the EXV valve body with the hand. As the valve drives open, a soft, smooth pulse will be felt for approximately 26 seconds as the valve travels from fully closed to fully open. When the valve reaches the end of its opening stroke, a hard pulse will be felt momentarily. Drive the valve closed and a soft, smooth pulse will be felt for the 26 seconds necessary for the valve to travel from fully open to fully closed. When the valve reaches the end of its stroke, a hard pulse will again be feelt as the valve overdrives by 50 steps. The valve should be driven through at least 2 complete cycles to be sure it is operating properly. If a hard pulse is felt for the 26 second duration, the valve is not moving and should be replaced.

20

Page 20
Image 20
Carrier HS070-160 manual Thermistor Locations

HS070-160 specifications

The Carrier HS070-160 is a high-efficiency air conditioning unit renowned for its robust performance and advanced technological features, making it an optimal choice for both commercial and industrial applications. This model is a part of Carrier's commitment to providing reliable and energy-efficient climate control solutions tailored to meet diverse cooling needs.

One of the standout features of the HS070-160 is its impressive cooling capacity, which ranges from 70 to 160 tons. This range makes it suitable for various environments, from large office buildings to manufacturing facilities. The unit is designed with versatility in mind, offering the option for both air-cooled and water-cooled configurations, thereby allowing users to choose the most suitable setup for their specific installation needs.

The HS070-160 incorporates a state-of-the-art variable speed drive technology, which enables the compressor to adjust its speed according to the cooling demand. This not only results in enhanced energy efficiency but also improves overall comfort by providing more consistent temperature control. Additionally, the unit features high-efficiency scroll compressors that further improve its performance while minimizing energy consumption.

In terms of construction and durability, the HS070-160 is built to withstand harsh environmental conditions. The unit is equipped with corrosion-resistant coatings and sturdy components, ensuring longevity and reliable operation across a broad range of settings. The design also promotes ease of maintenance, with accessible service points that simplify routine checks and repairs.

Another noteworthy characteristic of the Carrier HS070-160 is its advanced control systems. The unit can be integrated with smart building management systems, allowing for precise monitoring and control of HVAC operations. This integration helps facility managers optimize energy usage and reduce operational costs while maintaining comfortable indoor climates.

Furthermore, the HS070-160 adheres to stringent environmental standards, making it an eco-friendly choice. It is compatible with low-GWP refrigerants, aligning with global efforts to reduce greenhouse gas emissions.

In conclusion, the Carrier HS070-160 combines efficiency, durability, and advanced technology, making it a top contender for businesses looking to invest in dependable air conditioning solutions. Its comprehensive features and characteristics not only enhance performance but also contribute to significant energy savings and environmental sustainability.