Carrier HS070-160 Display Codes, Operating Modes, Alarms, Action, Description, Probable Cause

Models: HS070-160

1 28
Download 28 pages 34.06 Kb
Page 9
Image 9
Table 7 - Display Codes

Table 7 - Display Codes

OPERATING MODES

 

 

 

ALARMS

 

 

 

Action

 

Reset

 

Display

Description

Taken Sv

 

Probable Cause

 

Method

 

 

Control

 

 

 

 

 

 

 

 

 

 

 

 

 

Comp

Al

Al

FailureCircuit

A

shut

off

M a n u a l

High pressure switch trip or high discharge gas temp

 

 

 

Failure

Comp

shut off

 

M a n u a l

switch trip, on when it is not supposed to be on. Wiring

Campo p

A2Bl

ii:

Failure

Circuit

B

shut

off

M a n u a l

error between electronic control and compressor relay.

Comp

 

B 2

Failure

Comp

shut off

 

M a n u a l

 

Loss of charge circuit A

 

Circuit

A

shut

off

M a n u a l

Low refrigerant charge, or loss of charge pressure switch

Loss of charge circuit B

 

Circuit

B

shut

off

M a n u a l

failure.

Low cooler flow

 

 

Unit shut

off

 

M a n u a l

No cooler flow or reverse cooler flow

Low oil pressure circuit A

Circuit

A

shut

off

M a n u a l

Oil pump failure or low oil level, or switch failure.

low oil pressure circuit B

Circuit

B

shut

off

m a n u a l

 

Freeze

protection

 

 

Unit shut

off

 

Auto.

Low cooler flow

High suction superheat circuit A

Circuit

A

shut

off

M a n u a l

Low charge or EXV failure, or plugged filter drier.

High suction superheat circuit B

Circuit

B

shut

off

M a n u a l

 

Low suction suoerheat circuit A

Circuit

A

shut

off

M a n u a l

EXV failure ar cooler thermistor error.

Low suction superheat circuit B

Circuit

6

shut

off

M a n u a l

 

Leaving

water

thermistor

failure

Unit shut

off

 

Auto.

Thermistor failure, or wiring error, or thermistor not

Entering

water

thermistor

failure

Use default value

Auto.

connected to input terminals.

Cooler thermistor failure circuit A

Circuit

A

shut

off

Auto.

 

Cooler thermostor failure circuit B

Circuit

B

shut

off

Auto.

 

Comp thermistor failure circuit A

Circuit

A

shut

off

Auto.

 

Comp thermistor failure circuit B

Circuit

B

shut

off

Auto.

 

Reset thermistor

failure

 

Stop reset

 

Auto.

 

NOTES:

1.Freeze protection trips at 35 F (1.7 C) for water and 6 degrees F (3.3 degrees C) below set point for brine units. Resets at 6 degrees above set point.

2.All auto. reset failures that cause the unit to stop will restart the unit when the error has been corrected.

3.All manual reset errors must be reset by moving the control switch to STANDBY then to RUN.

4.Valid resistance range for thermistors is 363,000 ohms to 216 ohms.