Table 20 Compressor Loading and Unloading Sequences
COOLING
STAGE
SIZE 034 UNITS
Lead Circuit Lag Circuit Active
Cylinders
Percent
Capacity
Comp 1 Unloader
U1
Unloader
U2 Comp 2
0OFF OFF OFF OFF 0 0
1ON ON ON OFF 2 17
2ON ON OFF OFF 4 33
3ON OFF OFF OFF 6 50
4ON ON ON ON 8 67
5ON ON OFF ON 10 83
6ON OFF OFF ON 12 100
COOLING
STAGE
SIZE 038 UNITS
Lead Circuit Lag Circuit Active
Cylinders
Percent
Capacity
Comp 1 Unloader
U1
Unloader
U2 Comp 2
0OFF OFF OFF OFF 0 0
1ON ON ON OFF 2 14
2ON ON OFF OFF 4 28
3ON OFF OFF OFF 6 42
4ON ON ON ON 6 72
5ON ON OFF ON 8 86
6ON OFF OFF ON 10 100