58
LEGEND AND NOTES FOR FIG. 57NOTES:
1.Connect TRAN1 to for 460 v units. Connect to for 230 v
units. If 208/230 v units are run with a 208 v power supply con-
nect to .
2.Connect TRAN2 to BLK lead for 460 v units. Connect to ORN
lead for 230 v units. If 208/230 v units are run with a 208 v
power supply connect to RED lead.
3.Circuit breaker must trip amps are equal to or less than 156%
FLA (full load amps) for CB1 and CB2. All others are 140%.
4.If any of the original wire furnished must be replaced, it must
be replaced with type 90° C wire or its equivalent.
5.Number(s) indicates the line location of contacts. A bracket
over (2) numbers signifies single pole double throw contacts.
An underlined number signifies a normally closed contact.
Plain numbers (no lines), signify a normally opened contact.
6.Condenser fan motors are thermally protected.
7.Three phase motors are protected under primary single phas-
ing conditions.
ALM —Alarm IGVM —Inlet Guide Vanes Motor
C—Contactor LAT —Leaving-Air Temperature
CB —Circuit Breaker LPS —Low-Pressure Switch
CCB —Control Circuit Breaker MTR —Motor
COMP —Compressor MV —Main Valve
CH —Crankcase Heater NC —Normally Closed
CR —Control Relay NO —Normally Open
DPS —Differential Pressure Switch OFC —Outdoor Fan Contactor
DPT —Discharge Pressure Transducer OFM —Outdoor (Condenser) Fan Motor
EAT —Enering-Air Temperature OMR —Outdoor Motor Relay
EC —Enthalpy Control PCB —Power Exhaust Circuit Breaker
ECR —Economizer Close Relay PEC —Power Exhaust Contactor
EOR —Economizer Open Relay PEDM —Power Exhaust Damper Motor
EQUIP —Equipment PEM —Power Exhaust Motor
FS —Fan Status Switch P, PL —Plug
GND —Ground RCB —Return Fan Circuit Breaker
HIR —Heat Interlock Relay RES —Resistor
HPS —High-Pressure Switch RFC —Return Fan Contactror
HR —Heater Relay RFM —Return Fan Motor
HTR —Heater SCT —Saturated Condensing Thermistor
IDC —Induced Draft Contactor TB —Terminal Block
IDM —Induced Draft Motor TRAN —Transformer
IFC —Indoor (Evaporator) Fan Contactor U—Unloader
IFCB —Indoor Fan Circuit Breaker VFD —Variable Frequence Drive
IFM —Indoor Fan Motor Field Wiring
IGV —Inlet Guide Vanes Factory Wiring
H4 H3
H2