43
Table 20 Compressor Loading and Unloading Sequences (cont)
COOLING
STAGE
SIZE 044 UNITS
Lead Circuit Lag Circuit Active
Cylinders
Percent
Capacity
Comp 1 Unloader
U1 Comp 2
0OFF OFF OFF 0 0
1ON ON OFF 2 25
2ON OFF OFF 4 50
3ON ON ON 6 75
4ON OFF ON 8 100
COOLING
STAGE
SIZE 048 UNITS
Lead Circuit Lag Circuit Active
Cylinders
Percent
Capacity
Comp 1 Unloader
U1
Unloader
U2 Comp 2
0OFF OFF OFF OFF 0 0
1ON ON ON OFF 2 19
2ON ON OFF OFF 4 38
3ON OFF OFF OFF 6 58
4ON ON ON ON 6 62
5ON ON OFF ON 8 81
6ON OFF OFF ON 10 100
COOLING
STAGE
SIZE 054 UNITS
Lead Circuit Lag Circuit Active
Cylinders
Percent
Capacity
Comp 1 Unloader
U1
Unloader
U2 Comp 2
0OFF OFF OFF OFF 0 0
1ON ON ON OFF 2 20
2ON ON OFF OFF 4 40
3ON OFF OFF OFF 6 60
4ON ON OFF ON 10 80
5ON OFF OFF ON 12 100
COOLING
STAGE
SIZE 064 UNITS
Lead Circuit Lag Circuit Active
Cylinders
Percent
Capacity
Comp 1 Unloader
U1
Unloader
U2 Comp 2
0OFF OFF OFF OFF 0 0
1ON ON ON OFF 2 17
2ON ON OFF OFF 4 33
3ON OFF OFF OFF 6 50
4ON ON ON ON 8 67
5ON ON OFF ON 10 83
6ON OFF OFF ON 12 100
COOLING
STAGE
SIZE 074, 078 UNITS
Lead Circuit Lag Circuit Active
Cylinders
Percent
Capacity
Comp 1 Unloader
U1
Unloader
U2 Comp 2
0OFF OFF OFF OFF 0 0
1ON ON ON OFF 2 14
2ON ON OFF OFF 4 29
3ON OFF OFF OFF 6 43
4ON ON ON ON 8 71
5ON ON OFF ON 10 86
6ON OFF OFF ON 12 100