POWER EXHAUST FAN MOTOR NO. 1 OVERLOADPROTECTION — The VFD provides operating overloadprotection for the supply fan motor. The factory has pro-grammed the power exhaust VFD overload function to matchthe factory-installed motor (motor size and efficiency). If thepower exhaust fan motor is changed from the original factoryselection, the overload value may need to be changed by theservice person. Contact your local Carrier representative forassistance in determining the proper overload setting.NOTE: Variable frequency drive size is matched to factory-installed motor size. Do not increase motor size without alsochanging to equivalent VFD size.Table 33 Carrier Power Exhaust VFD Default Program Parameter Values
*These settings differ from the Toshiba defaults and are required for Carrier applications.
NOTE: To restore original factory settings, change tYP to 6 in SEtup mode (SEtP).
This restores the VFD original factory settings.
PARAMETER GROUP PARAMETER DEFAULT VALUE
SEtP
(Setup)
ACC1 60.0 Sec
DEC1 60.0 Sec
UL 59.8 Hz
LL 10.0 Hz*
Luln 1
P3 20%
F-P3 0.0 Hz
P4 98%
F-P4 60 Hz
tHr1 See Table 35
StC1 0
StL1 110%
OLN 1
tYP 5*
Gr.F
(Fundamental)
FH 60 Hz
Pt 12
Gr.Fb
(Feedback)
FbP1 1*
Fbin 2
GP .30
Gl 2 sec
GA 0
GFS 80
P1LL 10
PuL 1
PuUl 10
PuLL 10
Gr.SF
(Frequency Settings) Fsor 60 Hz
Gr.Pn
(Panel Control) Fr 0*
Gr.St
(Terminal Selection)
1t 1
1t0 0
1t1 56
1t2 13
1t3 3
1t4 10
Ot1 4*
Ot2 2*
Ot2d 5*
Ot2H 100*
LF 15*
Gr.Pr
(Protection)
UuC 1*
UuCt 2
ArSt 3
Gr.Ut
(Utility)
Cnod 1*
Fnod 2*
bLPn 1*
4-20mA
P24 RES RR F
ST FM AMCC CC
RSI
RX
S2 S3
PP
S4 RCH P24 LOWLOW
FLA
FLB
FLC
FP
IV
C
A
Fig. 56 Variable Frequency Drive Terminal Block