MOUNTING AND WIRING THE SAFETY REVERSING SENSORS

Slide a 1/4"-20x1/2" carriage bolt head into the slot on each sensor. Use wing nuts to fasten safety reversing sensors to brackets, with lenses pointing toward each other across the door. Be sure the lens is not obstructed by a bracket extension (Figure 5).

Finger tighten the wing nuts.

Run the wires from both safety reversing sensors to the operator. Use insulated staples to secure wire to wall and ceiling.

Strip 7/16" (11 mm) of insulation from each set of wires. Separate white and white/black wires sufficiently to connect to the operator quick-connect terminals: white to white and white/black to grey (Figure 6).

ALIGNING THE SAFETY REVERSING SENSORS

Plug in the operator. The indicator lights in both the sending and receiving eyes will glow steadily if wiring connections and alignment are correct.

The sending eye amber indicator light will glow regardless of alignment or obstruction. If the green indicator light in the receiving eye is off, dim, or flickering (and the invisible light beam path is not obstructed), alignment is required.

Loosen the sending eye wing nut and readjust, aiming directly at the receiving eye. Lock in place.

Loosen the receiving eye wing nut and adjust the safety reversing sensor until it receives the sender’s beam. When the green indicator light glows steadily, tighten the wing nut.

Figure 5

Wing Nut 1/4"-20

Carriage Bolt

1/4"-20x1/2"

Lens

TROUBLESHOOTING THE SAFETY REVERSING SENSORS

1.If the sending eye indicator light does not glow steadily after installation, check for:

Electric power to the operator.

A short in the white or white/black wires. These can occur at staples, or at operator connections.

Incorrect wiring between safety reversing sensors and operator.

A broken wire.

2.If the sending eye indicator light glows steadily but the receiving eye indicator light doesn’t:

Check alignment.

Check for an open wire to the receiving eye.

3.If the receiving eye indicator light is dim, realign either sensor.

NOTE: When the invisible beam path is obstructed or misaligned while the door is closing, the door will reverse. If the door is already open, it will not close.

Bell Wire

Figure 6

 

 

 

 

 

Motor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bell Wire

To CableTension Monitor

Connect Wire to

Quick-Connect

Terminals

Sensor

Connections

WHT/REDWHT/BLK

WHTWHT

To Door Control

Quick-Connect Terminals

 

To insert or release wires, push in tab with screwdriver tip.

Safety Reversing Sensor

 

 

 

Invisible Light Beam

 

Protection Area

Safety R

eversing Sens

or

16