T E S T I N G

TEST PROCEDURES

TO BE PERFORMED BY FACTORY AUTHORIZED PERSONNEL ONLY! CLEAR FIRE DOOR OPENING AND PROHIBIT TRAFFIC THROUGH DOOR OPENING WHILE TESTING!

Testing does not affect normal operation of alarm system when connected to release device/control panel. Testing of the release device is independent of, and shall in no way be interpreted as an alternative method of, testing of a central fire alarm system, motorized operator and/or any other system component employed on the fire door or counter fire door installation. Complete testing and normal operation can only be accomplished with power applied to unit. Door must be in open position with power applied to unit to begin testing. The following procedures describe testing of all options. Verify options ordered and installed with unit. All tests may not apply. Refer to Figure 1 for location of all the LEDs and switches mentioned in this section.

INITIAL POWER UP

1.Apply line power to the release device.

2.Power LED (red) will be lit on the bottom of the release device.

WARNING

To prevent possible SERIOUS INJURY or DEATH:

Clear fire door opening and prohibit ALL traffic through door opening while testing.

Test every 90 days to assure proper operation of release device.

FIGURE 1

Mechanical

Reset Plunger

MECHANICAL RELEASE

1.Depress and continue to hold test button on side of release device. After the selected delay expires, the device will release the end link and allow door to drop. Release test button.

2.Reset the door per door manufacturer’s instructions. Raise door and then reset the release device by pushing downward on the mechanical reset button at the top of the device. Fully insert the end link through the side opening on the device and release the reset button in order to latch end link.

CLOSE DOOR DETECTION (OPTIONAL)

1.Using the chain hoist or motor operator, lower the door to fully closed position.

2.Verify that Close Door Detection LED (yellow) is lit indicating door closure. Depress and continue to hold test button on side of release device for 10 seconds. Close Door Detection logic will prohibit the release device from energizing and releasing the end link. Reset the test button.

3.Raise door to fully open position.

SUSPENSION OF POWER

Front of Release Device

 

End Link

 

Electronic

Bottom of Release Device

Reset Button

 

 

Test Button

 

Red LED (Line Power Present)

 

Yellow LED

 

(Close Door Detection

 

Release Disabled)

1.Make sure door is in fully open position. Turn off all power to release device. Immediately upon loss of power to the release device, a mechanical release will be initiated.

2.Reset the door per door manufacturer’s instructions. Raise the door and then reset the release device by pushing downward on the mechanical reset button at the top of the device. Fully insert the end link through the side opening on the device and release the reset button in order to latch end link. Press the “Reset” button on the side of the device to reset the alarm loop.

After completing all tests, make sure the door is in its normal condition (open or closed) and all power required for normal operation is restored to unit. The release device is designed to operate with power applied.

NOTE: Testing shall be performed and witnessed for proper

 

operation.