CONNECTIONS OF INITIATING DEVICES AND ACCESSORIES

W I R I N G

WARNING

A maximum of 4 smoke detectors may be installed with this device. Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage. End-of-line devices must be installed for supervision of electrical power to

4-wire smoke detector. When using 4-wire smoke detectors with this device, electrical supervision must be provided by means of a

To prevent possible SERIOUS INJURY or DEATH:

End-of-line devices MUST be installed for supervision of electrical power to 4-wire smoke detector.

DO NOT install this device on a motorized door without an electric safety edge.

UL/ULC listed end-of-line relay.

NOTE: For low voltage wiring #18 AWG is recommended.

Normally Open “2-Wire,” Class B Style A Initiating Devices

Connect wiring from N/O initiating device loop to positions 3 and

4. Place the supervisory resistor (10k ohm @ 1/2 watt) contained

within the accessory pack. (Figure 3). Observe proper polarity, 3

(+), 4 (–) when attaching to the release device’s terminal board.

NOTE: Make certain that the factory-installed jumper between

terminal positions 5 and 6 remains in place. This option is a

supervised, current-limited circuit.

FIGURE 3

24Vdc Power from Terminal Strip

3

4

IN/OUT – OUT + IN +

10k Ohm @1/2 watt Supervisory Resistor (LMEOLRES-10)

IN/OUT – OUT + IN +

NOTE: Follow this method of attachment when using LM2W-B, LM2WT-B, or other 2-wire 24Vdc smoke detectors.

OR

FIGURE 4

NOTE: Follow this method of attachment when using

(–)

LM4W-B, LM4WT-B, or other N/O 4-wire smoke detectors.

 

Normally Open “4-Wire,” Class B Style A Initiating Devices

Connect wiring from N/O 4-Wire initiating device loop to positions 3 and 4, making sure an end-of-line supervisory resistor (10k ohm @ 1/2 watt) is installed as shown in Figure 4 or 5, depending upon the type of smoke detector being used. Observe proper polarity, 3 (+), 4 (–) when attaching to the release device’s terminal board. NOTE: Make certain that the factory- installed jumper between terminal positions 5 and 6 remains in place. This option is a supervised, current-limited circuit.

Power from Control Panel

(+)

Terminal Strip

3

4

COM NO IN/OUT – OUT + IN +

COM NO IN/OUT – OUT + IN +

LMEOLR1224

12/24 Vdc

EOL Relay

10k Ohm @ 1/2 watt Supervisory Resistor (LMEOLRES-10)

OR

Normally Closed “4-Wire,” Class B Style A Initiating Devices

After removing the factory-installed jumper between terminal positions 5 and 6, connect wiring from N/C 4-Wire initiating device loop to positions 5 and 6 (Figure 6). This option is a supervised, current-limited circuit. NOTE: Make certain that the factory-installed resistor between positions 3 and 4 remains in place.

NOTE: End-of-line devices must be installed adjacent and after the last initiating device. Initiating device loops are supervised and cannot be direct series or paralleled between multiple release devices or shared with other alarm equipment. For proper wiring configurations from multiple smoke detectors or signaling for simultaneous closure on multiple doors, call technical support, 1-888-528-7870. Incorrect wiring between devices may cause damage to the release control circuit and void warranty.

OR

Relay Module Installation as described on the following page.

FIGURE 5

NOTE: Follow this method of attachment when using

(+)

LM1424,

LM1412, or other N/O 4-wire smoke detectors.

 

 

 

 

Power from

 

 

 

Control Panel

 

 

 

(–)

 

 

 

LMEOLR1224

 

 

 

 

 

(+)

 

(+)

12/24 Vdc

 

Alarm

(–)

 

EOL Relay

 

Contacts

 

(–)

 

 

 

 

 

Style A

 

 

 

 

(N/O)

 

 

 

Terminal Strip

 

 

10k Ohm @ 1/2 watt

 

 

Supervisory Resistor

(+)

 

 

 

(LMEOLRES-10)

 

 

 

 

3

 

 

 

 

4

(–)

IMPORTANT: When using 4-wire smoke detectors with this device, the smoke detectors must be powered from a source other than the release device, such as an approved UL 1481 regulated power supply providing battery backup support.

FIGURE 6

(–)

Power from

 

 

NOTE: Generic version of a N/C

Control Panel

 

 

4-wire smoke detector is shown.

(+)

 

 

 

(+)

 

(+)

 

 

 

(–)

 

(–)

 

 

 

 

N/C

N/C

C

LMEOLR1224

C

 

12/24 Vdc

 

 

 

 

 

 

EOL Relay

Terminal Strip

Purple

 

5

IMPORTANT: When using 4-wire smoke detectors with this device, the smoke detectors must be powered from a source

6other than the release device, such as an approved UL 1481

regulated power supply providing battery backup support.

7