M A I N T E N A N C E
MAINTENANCE REQUIREMENTS
The release device has no scheduled maintenance requirements. The unit has been designed and tested for use in dry, indoor locations. Testing of the unit at least once every 90 days is recommended, but test intervals shall ultimately be subject to criteria established by the Authority Having Jurisdiction (AHJ).
WARNING
To avoid SERIOUS PERSONAL INJURY or DEATH from electrocution, disconnect ALL power BEFORE performing ANY maintenance.
FIGURE 1
Mechanical
Reset Plunger
Front of Release Device
| End Link |
| Electronic |
Bottom of Release Device | Reset Button |
| |
| Test Button |
| Red LED (Line Power Present) |
| Yellow LED |
| (Close Door Detection |
| Release Disabled) |
ENCLOSURE MOUNTED LEDS STATUS INDICATORS
LED Label | LED Color | Description | Action Required | |
Disable |
| Yellow | The Yellow LED will light when the door reaches the close | If the LED does not light when the door reaches the close |
|
|
| limit and activates a proximity switch attached to terminal | limit and activates the proximity switch, then check that |
|
|
| positions 7 and 8 on the release device. This | the proximity switch has been activated and that the |
|
|
| configuration results in the device not releasing the | switch is set to normally open (N.O.). Check to make |
|
|
| fusible link assembly in alarm or power loss situations | certain that the switch is attached to terminal positions 7 |
|
|
| and should only be used when the fire door is kept in a | and 8 on the release device. |
|
|
| constant closed position. |
|
|
|
|
|
|
Power |
| Red | If the Red LED is lit, then the line power is connected and | If the LED does not light when power is applied, check |
|
|
| switched “on.” | that power is connected as described in the installation |
|
|
|
| manual electrical connections. |
|
|
|
|
|
12