I N S T A L L A T I O N
IMPORTANT INSTALLATION INSTRUCTIONS WARNING
To reduce the risk of SEVERE INJURY or DEATH:
1.READ AND FOLLOW ALL INSTALLATION WARNINGS AND INSTRUCTIONS.
2.NEVER connect release device to power source until instructed to do so.
3.DO NOT install this device on a motorized door without an electric safety edge.
Classification:
Releasing device as defined by Underwriters Laboratories.
Installation Requirements:
4.DO NOT use this device without fuse links installed.
5.Concrete anchors MUST be used if mounting release device into masonry.
6.DO NOT exceed maximum pull rating of 40 lbs. on releasing device.
Mechanical
Reset Plunger
Intended for “Indoor Dry” locations; all wiring must be performed in accordance with the most current version of NFPA 72 - National Fire Alarm Code and the National Electric Code.
MOUNT THE RELEASE DEVICE
Installation procedures vary according to door types. Refer to door manufacturer’s recommendation that applies to your door.
1. | Mount the release device on a vertical surface with chain end |
| link exiting side of enclosure. |
2. | Secure the release device enclosure with fasteners (#10 is the |
| minimum size recommended). If installing in masonry, use |
| concrete anchors (not provided). |
Eyebolt
End Link
Fuse Links
3. Install hardware (sash chain or 1/16 cable, |
links, |
Smoke Detector
Turnbuckle
| manufacturer’s recommendations. NOTE: The end link direction |
| of pull must be perpendicular to the side of the release device |
| enclosure. Install an eyebolt a minimum distance of 12" from |
| the release device to adequately redirect sash chain pull. |
4. | Install end link by pressing mechanical reset to allow insertion |
| of end link. Push end link completely in and release mechanical |
| reset to latch end link. |
5. | Remove sash chain or cable slack by adjusting turnbuckle. |
Chain End
Releasing Link
Unit
Chain
Fire Door
4