I N T R O D U C T I O N
AGENCY REQUIREMENTS
Installation and testing to factory specifications shall be performed by factory authorized personnel for proper operation in accordance with the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical Code (NEC), local, state, county, district and/or other applicable building and fire standards, guidelines, regulations and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).
SPECIFICATIONS
WARNING
To prevent possible SERIOUS INJURY or DEATH:
•DO NOT use this device without fuse links installed.
•Test every 90 days to assure proper operation of release device.
ELECTRICAL SPECIFICATIONS
VOLTAGE RATING: | 24Vdc |
STANDBY CURRENT: | .100A |
ALARM CURRENT: | .15A |
INITIATING DEVICE: | Maximum line impedance 20 ohm; |
| Maximum current not to exceed |
| .010A.; Maximum voltage 28Vdc |
COMMON ALARM AND |
|
TROUBLE RELAY: | .5A 125Vac, 60Hz |
(MAX. CONTACT RATING) | 1A 24Vdc Resistive |
| MECHANICAL SPECIFICATIONS |
| |
LOAD RATING: | Support and Release 40 lbs. Max. | WEIGHT: | Approximately 8 lbs. |
PHYSICAL DIMENSIONS: | 9.7" x 7.5" x 5" (h x w x d) |
|
|
PREPARATION
It is imperative that the wall or mounting surface provide adequate support for the release device.
Eyebolt
Fuse Links
Refer to the door manufacturer’s recommendations for use of this product with specific door being utilized. Use only hardware
Smoke Detector
Turnbuckle
approved or recognized by the appropriate testing and listing agencies in conjunction with the installation of this product.
Additional items may be required to complete the installation:
•Concrete anchors or fasteners
•Sash chain or 1/16 cable
•
•Fuse links
Chain End
Releasing Link
Unit
Chain
Fire Door
•Turnbuckles
•Smoke detectors (up to 4 may be installed with this device)
Refer to NFPA 72 and NFPA 80 for instructions concerning proper placement and detection coverage.
3