indicate it is acceptable for outdoor use.

6.Make sure the extension cord is properly wired and in good electrical condition. Always replace a damaged extension cord or have it repaired by a qualified electrician before using it.

7.Protect the extension cords from sharp objects, excessive heat, and damp or wet areas.

RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*

(110/220 VOLT)

NAMEPLATE

EXTENSION CORD

 

LENGTH

 

AMPERES

 

 

25’

50’

75’

100’

150’

(at full load)

 

 

 

 

 

 

 

 

 

 

 

0 – 2.0

18

18

18

18

16

2.1

– 3.4

18

18

18

16

14

3.5

– 5.0

18

18

16

14

12

5.1

– 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1

– 16.0

14

12

10

-

-

16.1

– 20.0

12

10

-

-

-

* Based on limiting the line

TABLE A voltage drop to five volts at 150% of the rated amperes.

Symbology

Double Insulated

 

Canadian Standards Association

 

 

 

Underwriters Laboratories, Inc.

 

 

V~

Volts Alternating Current

A

Amperes

 

 

 

n0 xxxx/min.

No Load Revolutions per Minute

(RPM)

Specifications

Electrical

120 V~ / 60 Hz / 620 W

Requirements

2-Prong, Polarized Power Plug

Speed

n0 750/min

Blows Per

2920 BPM

Minute

 

Capacity

1”

 

 

Chuck Type

SDS

Rotation

Clockwise (non-reversible)

 

For drilling stone, concrete, and

Applications

other hard and brittle materials.

 

For chiseling.

 

Wrench

 

SDS Drill Bits: 10mm/12mm

 

14mm/22mm

 

4-Point Chisel

Accessories

Container of Grease

 

Carbon Brush Set

 

Depth Gauge Rod

 

Auxiliary Handle

 

Carrying Case

 

E194601

Unpacking

When unpacking, check to make sure that the item is intact and undamaged. If any parts are missing or broken, please call Harbor Freight Tools at the number shown on the cover of this manual as soon as pos- sible.

SKU 97743

For technical questions, please call 1-800-444-3353.

Page 8

Page 8
Image 8
Chicago Electric 97743 operating instructions Specifications, Unpacking, Symbology, 25’ 50’ 75’