Product Overview
The show environment table command displays the temperature and voltage thresholds for each of the three RSP2 temperature sensors, for each monitored status level: low critical, low warning, high warning, and high critical, which are the same as those listed in Tables 2 and 3. The slots in which the RSP2 can be installed are indicated in parentheses (6 and 7). Also listed are the shutdown thresholds for the processor boards and power supplies. Following is sample output of the show env table command:
Router# show env table
Sample Point | LowCritical | LowWarning | HighWarning | HighCritical | |
RSP(6) Inlet |
|
| 44C/111F | 50C/122F | |
RSP(6) Hotpoint |
|
| 54C/129F | 60C/140F | |
RSP(6) Exhaust |
|
|
|
| |
RSP(7) Inlet |
|
| 44C/111F | 50C/122F | |
RSP(7) Hotpoint |
|
| 54C/129F | 60C/140F | |
RSP(7) Exhaust |
|
|
|
| |
+12 | Voltage | 10.76 | 11.37 | 12.64 | 13.24 |
+5 Voltage | 4.49 | 4.74 | 5.25 | 5.52 | |
Voltage | |||||
+24 | Voltage | 19.06 | 21.51 | 26.51 | 28.87 |
Shutdown boards | at | 101C/213F |
|
| |
Shutdown power supplies at | 101C/213F |
|
|
Note Temperature ranges and values are subject to change.
The show environment all command displays an extended report that includes the arbiter type, backplane type, power supply type (AC or DC), wattage and status, the number and type of intermittent power failures (if any) since the system was last powered on, and the currently measured values at the RSP2 temperature sensors and the
Note The current monitor circuits of the 7513 power supply are only accurate at high power levels. They are there to prevent
Active fault conditions are indicated when the blower or power supply has failed or is not present (as “Blower #3” indicates in the following example). The system expects to see three blowers or fans in the Cisco 7513: the main system blower, and one fan in each power supply. The system blower is designated #1, the power supply fan in power bay A is #2, and the power supply fan in power bay B is #3. The active fault condition in the following example shows that there is no power supply installed in power bay B because the display indicates that power supply #2 (in power bay B) is removed. System blower speed is displayed as a percentage of maximum.
There are four active trip points: restart OK, temperature warning, board shutdown, and power supply shutdown. (There are no active trip points shown in the following example.) The soft shutdowns refer to the number of times the system will reset itself before it executes a complete chassis (or hard) shutdown.
The current temperature measurements at the three RSP2 sensors are displayed as inlet, hotpoint, and exhaust. The shutdown temperature source is the hotpoint sensor, which is located toward the center of the RSP2. System voltage measurements are also displayed, followed by the system current measurements and power supply wattage calculation. Following is sample output of the show env all command:
Router# show env all
Arbiter type 1, backplane type 7513 (id 2)
Upgrading the
| 11 |
| |
|
|