Connecting the System Ground

Figure 6

Installing the Rubber Feet

KO

KO

 

N

KO

AF

TU PIN

 

 

TUPTU O

-

+

o

KO

KO

 

NAF

TU PIN

KO

 

 

TUPTUO

-

+

o

147981

Connecting the System Ground

The system (NEBS) ground provides additional grounding for EMI shielding requirements and is intended to satisfy the Telcordia Technologies NEBS requirements for supplemental bonding and grounding connections.

Note The ground lug and the ground lug screws are supplied as part of the accessory kit. The ground wire and the required tools are not supplied as part of the accessory kit.

To assemble and connect the system ground, you need the following tools and materials:

Ground lug—A two-hole standard 90-degree barrel lug. Supports up to 6 AWG wire.

Ground screws—Two M4 x 8-mm pan-head screws.

Ground wire—The ground wire should be sized according to local and national installation requirements. Commercially available 12 AWG to 6 AWG wire is recommended. The length of the ground wire depends on the proximity of the switch to proper grounding facilities.

Number 1 Phillips screwdriver.

Wire-stripping tool to remove the insulation from the ground wire.

Crimping tool to crimp the ground wire to the ground lug.

To assemble the ground lug and cable and attach them to the ground pad (see Figure 7), follow these steps:

Step 1 Use a wire-stripping tool to remove approximately 0.75 inch (19 mm) of the covering from the end of the ground wire.

Step 2 Insert the stripped end of the ground wire into the open end of the ground lug and crimp the barrel of the ground lug. Verify that the ground wire is secure in the ground lug.