Cleveland Range KDL-TSH, KDL-SH, KDP-T manual Steam Requirements For Kettles, Steam Pipe Sizing

Models: KDP-T KDL-T KDL-SH KDP KDL-TSH

1 19
Download 19 pages 16.12 Kb
Page 5
Image 5
STEAM REQUIREMENTS FOR KETTLES

STEAM REQUIREMENTS FOR KETTLES

Kettle Cap.

Kettle

 

25 psi Steam 265°F

 

40 psi Steam 287°F

80 psi Steam 302°F

U.S. Gal.

Dia.

Lbs./Hr.

Hp./Hr.

Lbs./Hr.

Hp./Hr.

Lbs./Hr.

Hp./Hr.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

26"

100

3

 

120

4

 

150

4.5

 

60

29.5"

150

4.5

 

190

5.5

 

230

7.0

 

80

33"

210

6.0

 

260

7.5

 

300

9.0

 

100

36"

260

7.5

 

320

9.5

 

390

11.0

 

125

40"

320

9.5

 

400

11.5

 

470

14.0

 

150

40"

390

11.0

 

480

14.0

 

570

17.0

 

￿Steam requirements are maximum per hour.

￿If more than one unit is on the same line then add the steam usage for each one to reach a total.

STEAM PIPE SIZING

Required pipe length in feet/meters

Steam Required

200 Ft.

400 Ft.

600 Ft.

Lbs./Kg. per hour

60 Meters

125 Meters

185 Meters

100/45 Kg.

3/4"

1"

1 1/4"

200/91 Kg.

1"

1 1/4"

1 1/2"

300/136 Kg.

1"

1 1/4"

1 1/2"

400/182 Kg.

1"

1 1/2"

1 3/4"

500/227 Kg.

1 1/4"

1 1/2"

1 3/4"

700/318 Kg.

1 1/2"

1 3/4"

2"

900/409 Kg.

1 1/2"

1 3/4"

2"

NOTES:

￿Pipe size in inches.

￿Less than 50 PSI (3.4 BAR) pressure, increase pipe size by 1/4".

￿80 to 100 PSI (5.5 to 6.8 BAR), Decrease pipe size by 1/4".

Page 5
Image 5
Cleveland Range KDL-TSH, KDP, KDL-SH Steam Requirements For Kettles, Steam Pipe Sizing, Required pipe length in feet/meters