Conair VL Series VL Air-cooledPortable Chillers 0.25 to 1.5 tons, 8.1SPECIFICATIONS, Model, VLA-1

Models: VL Series

1 44
Download 44 pages 5.24 Kb
Page 34
Image 34
8.1SPECIFICATIONS

8.1SPECIFICATIONS

VL Air-cooled Portable Chillers: 0.25 to 1.5 tons

MODEL

VLA-.25

VLA-.33

VLA-.5

VLA-.75

VLA-1

VLA-1.5

Performance characteristics

 

 

 

 

 

 

Capacity* tons

0.25

0.32

0.41

0.70

0.98

1.35

Compressor Hp {kW}

0.25 {0.19}

0.33 {0.25}

0.5 {0.37}

0.75 {0.56}

1 {0.75}

1.5 {1.1}

Pump Hp {kW}

0.25 {0.19}

0.25 {0.19}

0.25 {0.19}

0.25 {0.19}

0.5 {0.37}

0.5 {0.37}

Chilled water flowgpm {lpm}

0.6 {2.3}

0.8 {3.0}

0.9 {3.4}

1.7 {6.4}

2.4 {9.1}

3.6 {13.6}

Chilled water pressurepsi {bar}

60 {4.1}

60 {4.1}

60 {4.1}

60 {4.1}

60 {4.1}

60 {4.1}

Reservoir capacity gal {liters}

4 {15}

4 {15}

4 {15}

4 {15}

4 {15}

4 {15}

Dimensions in {mm}

 

 

 

 

 

 

Height

33 {838}

33 {838}

33 {838}

33 {838}

33 {838}

37 {940}

Width

18 {457}

18 {457}

18 {457}

18 {457}

18 {457}

19 {483}

Depth

24 {610}

24 {610}

24 {610}

24 {610}

24 {610}

25 {635}

Pipe size NPT in.

 

 

 

 

 

 

Process (to and from)

0.5

0.5

0.5

0.5

0.5

0.75

Condenser

Weight lb {kg}

 

 

 

 

 

 

Shipping§

150 {68}

150 {68}

170 {77}

205 {93}

210 {95}

220 {100}

Voltages full load amps**

 

 

 

 

 

 

115V/1 phase/60Hz

11

12

14

22

24

220V/1 phase/60Hz

8

11

12

15

Refrigerant

 

 

HCFC-22

 

 

 

SPECIFICATION NOTES

*Ton capacity at 12,000 BTU/ton @ 50°F leaving water temperature @ 115°F condensing temperature. Capacities may be ± 5% as reserved by the compressor manufacturer. Capacity multipliers are: 50°F - 1.00; 40°F - 0.80; 30°F - 0.60; 20°F - 0.40.

Hermetic reciprocating compressor.

Consult pump curve for exact characteristics relating to pump performances. § Unit weight crated for shipment

** No allowance for inrush. Service disconnect by owner. Full load amps must be used to size disconnects and supply conductors. Consult factory for 50hz operation.

Specifications can change at any time. Contact your Conair representative for the most current information.

Page: 34

VL Series Portable Chillers, 0.25 to 1.5 Tons

UGH020/0301

Page 34
Image 34
Conair VL Series manual VL Air-cooledPortable Chillers 0.25 to 1.5 tons, 8.1SPECIFICATIONS, Model, VLA-.25, VLA-.33, VLA-.5

FAQ

What is the ton capacity of the VL air-cooled portable chillers?

The ton capacity ranges from 0.25 to 1.5 tons.

What are the dimensions of the VL series portable chillers?

The dimensions vary by model, with heights ranging from 33 to 37 inches, widths ranging from 18 to 19 inches, and depths ranging from 24 to 25 inches.

What refrigerant is used in the VL series portable chillers?

The VL series uses HCFC-22 refrigerant.