Conair VL Series manual C.Description Of Parameters

Models: VL Series

1 44
Download 44 pages 5.24 Kb
Page 16
Image 16
C.DESCRIPTION OF PARAMETERS

Up Arrow

Down Arrow

UP

DOWN

ewpc902t

outManual background

SET

Output Status Light

Set Button

Press for less than

3 seconds to change setpoint.

Press for more than 4 seconds to access parameters.

2.UP: used to increase the setpoint value, as well as the parameter when in programming. When held down for a few seconds, the change rate accelerates.

3.DOWN: used to decrease the setpoint value, as well as the parameter when in programming. When held down for a few seconds, the change rate accelerates.

4.OUT: status light of the output, blinks when in setpoint display/change mode or during programming.

C.DESCRIPTION OF PARAMETERS

1.D1: setpoint differential. The switching differential (hysteresis) can be set with positive value (make on rise) or with negative value (make on fall). See parameter “HC1”.

2.LS1: lower set. This is the lower limit below which the user cannot change the setpoint; normally set at the lowest value recommended for the sensor.

3HS1: higher set. Similar to “LS1”, however setting an upper limit for the setpoint.

4.od: output delay. This provides a delay selection for the outputs in applications where noise may cause brief erroneous signals from the sensor to the controller. Factory set at “0”.

5.Lci: lower current input (for EWPC 902/R, EWPC 902/P and EWPC 902/T with current input only). Read-out corresponding to 4 mA input signal (factory set at 20 %R.H for EWPC 902/R).

6.Hci: high current input (for EWPC 902/R, EWPC 902/P and EWPC 902/T with current input only). Read-out corresponding to 20 mA input signal (factory set at 100 %R.H for EWPC 902/R).

7.CAL: CALibration. This offers an adjustment up or down of the read-out, if needed. Factory set at “0”.

Page: 16

VL Series Portable Chillers, 0.25 to 1.5 Tons

UGH020/0301

Page 16
Image 16
Conair VL Series manual C.Description Of Parameters

FAQ

What is the purpose of the UP and DOWN buttons?

The UP button is used to increase the setpoint value or parameter when in programming, while the DOWN button is used to decrease the setpoint value or parameter. Holding down either button for a few seconds will accelerate the change rate.

What does the OUT status light indicate?

The OUT status light blinks during setpoint display/change mode or programming.

How can I adjust the output delay?

The output delay provides a delay selection for the outputs in applications where noise may cause brief erroneous signals from the sensor to the controller. It is factory set at 0.5.