Cooper Lighting MPWC specifications SF1-Tamper-proof Torx-headfasteners

Models: MPWC

1 4
Download 4 pages 1.26 Kb
Page 2
Image 2
SF1-Tamper-proof Torx™-head fasteners

Fe a t u r es, Catalog Logic and Options

Ballasts

Fixtures are supplied standard with electronic ballasts. Magnetic, energy saving ballasts are available with T8 lamps only (LEOC8). An optional radio interference filter (RIF) is commonly used with magnetic ballasts to reduce radio interference with sensitive equipment.

Cir cuitry

All individual input circuits will be supplied with a quick disconnect module (QDM) to facilitate ease of maintenance and installation. GCO and FNL options are commonly run on separate circuits. Each will be supplied with a QDM, separate from the primary lamp sources and will require additional switching and wiring by others. All primary lamp sources are wired onto the same circuit unless specified otherwise (See Switching Controls).

Switc hing Contr ols

No switching option specified implies the fixture will ship with input leads left unwired for switch wiring to be completed in field as desired.

PS4-4-position pull chain switching. All primary lamps wired in sequence by following: lower lamps on, upper lamps on, all lamps on, all lamps off. (120V only, brushed nickel finish, installed in center of unit on bottom of power tray).

PS1D-2 position pull chain switch, controls the bottom lamp compartment only. (120V only, brushed nickel finish, installed in center of unit on bottom of power tray). Upper lamp compartment is on a separate circuit to be wired and switched at wall or as desired.

LVCP-Low voltage controller, patient controlled. Mounted inside unit for patient control of all primary lamps-upper and lower lamp compartments. Wired in sequence for lower lamps on, upper lamps on, all lamps on, all lamps off. Includes 1/4" phone jack type receptacle centered in bottom of wire way for input control by others or may be used with accessory MBC-momentary button cord switch (See accessories).

LVCF-Low voltage controller, facility controlled. Mounted inside unit, controller is left unwired for specific wiring/control requirements of facility. Includes 1/4" phone jack type receptacle, centered in bottom of wire way for input control by others or may be used with accessory MBC- momentary button cord switch (See accessories).

Other Options

EBP-The emergency battery pack option is a good candidate for facilities that do not have emergency generator systems. Test switch and indicator light will be installed on top of unit in middle of the power tray. (Not available with all options, consult customer service).

FNL- Fluorescent night-light, 2-pin (G23 Base), 7 or 9w twin tube lamp installed in center of upper compartment of fixture, uses a magnetic ballast. FNL is wired on a separate circuit. (Lamps by others).

GCO-Grounded convenience outlet. White in color on units with white finish; black in color on all other finish options, wired on a separate circuit. (120V only, maximum 10 amps, installed on bottom right side facing unit; add "L" for installation on left side of unit, GCOL).

GLR-Fuse and holder, Wired to primary lamp circuit only. (Consult customer service for additional fusing options).

NRL-White LED nurses chart reading light. Directed so as not to discomfort the patient while awake or sleeping. Switched separately via rocker switch, both lamp and switch located on the bottom of the power tray. White in color on units with white finish; black in color on all other finish options (120V only, installed on either the right or left side, facing unit; add "R" for installation on right side of unit, NRLR; add "L" for installation on left side of unit, NRLL).

RIF-Radio interference filter, for use with magnetic T8 ballast only. (1 per ballast). (Not available with all options, consult customer service).

SF1-Tamper-proof Torx™-head fasteners

DTP-Decorative Trim Panel. This option allows the user to specify a wide assortment of laminate patterns available from "Wilsonart® Laminate". The pattern is placed in the front panel of the MPWC. Can be matched to any interior decorating theme, furniture color or wood grain. Example: DTPWM-Decorative Trim Panel, Windsor Mahogany

MPWC

Accessories

MBC-Momentary button cord switch. May be used with LVCP or LVCF options to control lamps. All units are wired at factory as specified per catalog logic (See Switching Controls).

VRSD-Torx™-head tamper-proof screwdriver (for use with SF1 option)

Maint enance

The MPWC is designed to facilitate ease of maintenance. Its three part assembly makes for efficient installation. No tools are required for relamping or substituting electrical power trays on standard fixtures. When maintenance is required, simply loosen the two end thumbscrews and slide the partial clamshell, front lens assembly forward and off. The lamps and power tray will now be accessible and can be removed by quarter-turn fasteners. This assembly hangs suspended on the back pan while it is easily disconnected via a quick disconnect power connector. Spare units can speed the maintenance process by easily substituting the power tray, thus causing less disruption in the room.

Specifications and Dimensions subject to change without notice.

ADC041675

Fail-Safe • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801

04/15/2007 12:56:42 PM

Page 2
Image 2
Cooper Lighting MPWC specifications SF1-Tamper-proof Torx-headfasteners

FAQ

What are the standard features of the Cooper Lighting MPWC?

The fixtures are supplied standard with electronic ballasts and can be equipped with various optional features such as radio interference filters, low voltage controllers, emergency battery packs, and more.

How do I switch between the primary lamps on the MPWC?

The MPWC offers various switching control options, including pull chain switches, low voltage controllers, and patient or facility-controlled configurations.

What maintenance procedures should be followed for the MPWC?

The MPWC is designed for ease of maintenance, with a three-part assembly that allows for efficient installation, relamping, and electrical power tray substitution without the need for tools.