Interconnecting Cables

Interconnecting cable conductor size is dependent upon the distance between the control, switches, and potential transformers. Maximum lengths of various cable combinations for No. 18 through No. 12 AWG conductors are shown in Table 2. The longest combination for the particular installation will determine the minimum conductor size. All cables are to be the same conductor size.

Note: If the control is equipped with the fault block accesso- ry, see Table 3 for additional cable length limitations.

On the switch end, the cables are wired to connector plugs provided as standard with the switches. On the S control end, the cables are wired either directly to terminal blocks in the control or to connector plugs provided with the Plugs and Receptacles accessory. Figure 9 shows the location of the accessory plugs and receptacles in the bottom of the control cabinet. See the appropriate switch installation manual for the location of the plugs and receptacles on the switch.

Switch Cable

A conductor cable is required between the S control and each high-voltage switch to operate the switches. This cable is wired to a socket plug at the switch end and to either a plug or TB1 at the control end. Pin identification, and cable OD and maximum conductor size accommodated by the plugs are shown in Figures 10 and 11.

Potential Transformer Cable

A four-conductor cable is required between the S control and the potential transformers to transmit source voltage intelligence and to supply operating power for the control. This cable is wired to a five-pin socket plug or TB2 at the control end. Pin socket identification, cable OD, and maximum conductor size accommodated by the plugs are shown in Figure 12.

Note: Connectors are not supplied for the transformer end of the cable.

TABLE 2

Maximum Control Cable Lengths

 

LOAD

 

HV

 

HV

SW

 

SW

1

 

2

B

S CONTROL

D

 

A

 

C

 

Maximum Length of

Cable Wire

Control Cable Combinations (ft.)

Size

VR, VLR, or VRV Switches

TSC Switch

(AWG)

A+B+D or C+B+D

A+B or A+D

 

 

or C+B or C+D

18

1450

1250

16

2300

2000

14

3700

3200

12

5900

5050

 

 

 

Note: The control cable lengths are not applicable for the C switch and the PST switch.

S260-75-1

Figure 9.

020079KM

Plugs and receptacles accessory.

 

 

 

KEYWAY

PIN F

 

PIN INSERT CONNECTIONS

INTO CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

VIEW A-A

 

 

 

RUBBER GROMMET

A

 

 

 

MAX. WIRE SIZE – NO.16 AWG

 

ACCOMMODATES

1/2" TO 5/8" DIA. CABLE

Figure 10.

Switch cable plug for VR, VLR, VRV, and TSC.

PST-6 8, 7, & 19 PIN RECEPTACLES

PST-9 8 & 19 PIN RECEPTACLES

 

 

 

KEYWAY

PIN INSERT CONNECTIONS INTO CONTROL

 

 

PIN F

 

 

 

 

 

 

 

 

 

A

A

G

A F

L M A

 

B H

F

B G E

K U N B

 

J T V P C

 

C

E

C D

H S R D

 

D

G F E

 

8 PIN

7 PIN

19 PIN

A

VIEW A-A

Figure 11.

Switch cable plugs for PST-6 and PST-9.

KEYWAY SOCKET INSERT – CONNECTS INTO CONTROL

SOCKET E

A

 

 

 

A

 

 

RUBBER GROMMET

 

 

 

 

 

 

ACCOMMODATES

 

MAX. WIRE

SIZE – NO.12 AWG

 

 

 

 

 

3/8" TO 1/2" DIA. CABLE

Figure 12.

PT cable plug.

13