Type S Automatic
5.Open SW1 and SW2 to simulate a backup clearing the fault.
The PREFERRED TO ALTERNATE TIMER will start and the preferred source
If alternate source switch (HV2) closes and the latch relay (R1) contacts are not opening, check for open contact between Accessory Tie Board tabs P and R (Source I HV switch) and tabs S and T (Source II HV switch).
6.Place OPERATION SELECTOR SWITCH (S3) to manual, and operate MANUAL OPER SOURCE I switch (S1) and MANUAL OPER SOURCE II switch (S2) to CLOSE.
HV switch (HV1 or HV2) will not close.
If either switch closes and the latch relay (R1) con- tacts are not opening, check for open contact between Accessory Tie Board tabs P and R (Source I HV switch) and tabs S and T (Source II HV switch).
7.Close test switch SW2 to restore preferred source voltage to the control. After the ALTERNATE TO PREFERRED TIMER runs out, reset the fault block accessory per instructions on the front panel.
The FAULT BLOCK OPERATED light will go out and the preferred source
If the FAULT BLOCK OPERATED light does not go out, the problem is most likely in the TRIP RESET BOARD.
Follow steps 8 through 11 to conduct a complete check involving all the phases of both
8.Connect the phases in series as shown in Figure 24 and retest.
Because of the series
If pickup current is other than 1/2 of setting, the polar- ity of a CT could be reversed.
9.Connect another two phases in series as shown in Figure 25 and retest.
Results should be the same as in preceding step 8.
AJUMPER
Figure 24.
Test Connections for Step 8.10.Repeat step 8 and 9 for the other
11.Remove the shorting jumper from the ground fault resistor upon completion of phase testing.
Ground Minimum Actuating CurrentWhen checking the ground minimum actuating current, the phase fault sensing portion of the accessory circuit must be disabled to prevent the possibility of erroneous test results. Proceed as follows:
1.Disable the phase sensing circuit by placing a short- ing jumper from the BLOCK tab on the phase resistor card to tab L on the accessory
2.Repeat steps 2 through 7 of the Phase Minimum Actuating Current test procedure.
Automatic Reset of Fault Block1.Close test switches SW2 and SW3 to supply voltage to the control.
The preferred source
2.Close SW1 and raise the test current until the FAULT BLOCK OPERATED lamp lights indicating that fault block has been activated.
3.Open SW2 to simulate the
The PREFERRED TO ALTERNATE TIMER will start to run.
4.Close SW2 to simulate reclosing of Source 1 back- up device. Quickly close SW1 and raise the test cur- rent to greater than 5 Amps but less than ground actuating level.
The FAULT BLOCK OPERATED lamp will go out in about
If FAULT BLOCK OPERATED lamp does not go out, the trouble is most likely in the
A
JUMPER
Figure 25.
Test Connections for Step 9.
34