Type S Automatic
TROUBLESHOOTING—BASIC S CONTROL
! | CAUTION: Equipment misoperation. Do not | |
energize this equipment until all control settings | ||
|
have been properly programmed and verified. Refer to the Control Programming and Operation section of this manual for programming procedures. Failure to comply can result in misoperation (unintended operation),
equipment damage, and personal injury. | G118.1 | |||
|
|
| ||
|
|
|
| |
! | WARNING: Hazardous voltage. Solidly ground | |||
all equipment. Failure to comply can | result in | |||
|
death, severe personal injury, and equipment damage.
T223.2
General
This troubleshooting guide is intended to assist in localizing problems that may be encountered in the operation of the
Schematic diagrams, Figures 16 and 17, are used as references throughout this guide. The physical location of the various circuit components and terminals are identified in Figure 27.
Remove the Control from Service
! | DANGER: Hazardous voltage. Contact with haz- | |
ardous voltage will cause death or severe per- | ||
|
sonal injury. Follow all locally approved safety procedures when working around high and low voltage lines
and equipment. | G103.3 |
The following warning only applies to controls equipped with the Fault Block Accessory:
! | WARNING: Hazardous Voltage. | |
switchgear before attempting to disconnect con- | ||
|
trol cable from control. Failure to do so may result in contact with high voltage pulse (300V peak) from the CT protection circuit. Failure to
death or severe personal injury. | G124.0 |
1.
2.Disconnect cables from the control.
Basic Troubleshooting
A quick check of the basic transfer operation while the control is in service can be made using the following procedure:
Source I or Source II Preferred Operation
1.Set CONTROL MODE switch (S5) to TEST. This wilI remove the control from service and allow it to operate without operating the
2.Check LATCH RELAY STATUS TEST terminals
3.Remove preferred source voltage by unscrewing one of the phase fuses from the applicable source. The PREFERRED TO ALTERNATE TIMER will start.
4.When the timer runs out, the latch relay (R1) will transfer; indicated by a transfer of the 120 Vac signal at the test terminals.
5.Replace the removed fuse to
IMPORTANT: If Control Mode Switch S5 is placed in the “Normal” position, the
6.When the timer runs out, the latch relay (R1) will transfer back to its original operating position.
7.Return the CONTROL MODE switch (S5) to NOR- MAL to return the control to service.
20