Cornelius R-134A manual General Maintenance, Adjustments, Sanitizing Syrup Systems

Models: R-134A

1 26
Download 26 pages 33.21 Kb
Page 16
Image 16

GENERAL MAINTENANCE

ADJUSTMENTS

ADJUSTING CO2 REGULATORS

The Operator must first check the CO2 supply to make sure it is adequate. Determine by looking at the CO2 cylinder primary CO2 regulator assembly 1800-psi gage as described in “Daily Pre-Operation Check”. Ranges for adjusting CO2 regulators are as follows: 80-psi minimum to a maximum of 125-psi for the carbonator primary CO2 regulator, 55 to 60-psi for sugar syrup tanks CO2 regulator, and 12-psi for diet syrup tank CO2 regulator. Refer to step 2 of “Maintenance Schedule”.

ADJUSTING CARBONATOR WATER TANK LIQUID LEVEL

The carbonator water tank liquid level (40 to 60-ounces) pump cut-in and cut-out were adjusted at the factory and should require no further adjustment. If incorrect adjustment is suspected, check and make necessary ad- justments as instructed in Service Manual (P/N 312021-004). Refer to step 3 of “Maintenance Schedule”.

SANITIZING SYRUP SYSTEMS

The syrup systems should be sanitized every 90-days as instructed in this manual. Refer to step 4 of “Mainte- nance Schedule”.

CHECKING ICE WATER BATH

(see Figure 3

A gurgle heard from the Cooling Unit indicates water level in the water tank is low and more water should be added for maximum cooling. Before adding more water to the tank, ice water bath and ice bank should be checked for cleanliness and water tank coils checked for excessive mineral deposit build-up. If necessary to clean the water tank, call a Service

Person to perform the cleaning procedure. Refer to step 5 of “Maintenance Schedule”. Add more water to the water tank as follows:

1.Place Cooling Unit power switch in “OFF”(down) position.

2.Remove top screw from ground strap securing hood to Cooling Unit.

3.Remove acorn nut securing hood on Unit, then lift hood straight up to remove.

4.Remove plug from drop-in refrigeration assembly water fill hole.

5.Using flashlight, inspect ice water bath and ice bank for cleanliness. Ice water bath should be clear and ice bank free of foreign particles.

6.If cleaning of water tank is necessary, call a Service Person to perform the cleaning procedure.

7.Fill water tank with clean water until water runs out of the water tank overflow tube. USE LOW-MINERAL-

CONTENT WATER WHERE A LOCAL WATER PROBLEM EXIST.

8.Install plug in water fill hole.

9.Install Cooling Unit hood and secure with acorn nut.

10. Install screw in hood ground strap to secure strap to hood.

13

312021002

Page 16
Image 16
Cornelius R-134A manual General Maintenance, Adjustments, Sanitizing Syrup Systems, Checking Ice Water Bath