clear of sharp objects. Further, ensure that the power cables or motor leads are not kinked. Never allow the power cables or motor leads to come in contact with oil, grease, hot surfaces, or chemicals. Utilize the two high temperature wires (red and white) provided by Country Flame to connect the air discharge snap disc to the electrical system as shown in FIGURE 14. Use the high temperature wire (green/yellow) to ground the fireplace to the right blower box. The green/yellow wire installed by Country Flame at the factory should be connected to one of the screws used to hold the air discharge snap disc to the fireplace. Connect the other end of the green/yellow wire to the right blower box or another earth ground coming from the circuit breaker box. The installing electrician should ensure proper grounding is accomplished for both blower boxes and the fireplace unit as per FIGURE 14. Screws and wire nuts are provided by Country Flame to ensure all parts are available during installation.

High temperature blower motor systems are lubricated at the factory and should require no further lubrication; however, at higher inlet temperatures, increased bearing life can be achieved by annually re-lubricating the motors with 10 to 20 drops of Anderol Number 465 high temperature synthetic lubricant. DO NOT USE petroleum-based oil, as bearing failure will result.