INGLENOOK GAS LOG KIT SPECIFCATIONS
TABLE 3 provides specifications for both Inglenook natural gas and propane gas fuel log kits. The installer and homeowner must understand the differences in these kits both for the type of fuel being used and the impact that altitude has on specific fuel operations. Test procedures for verifying the fuel pressures are provided as part of the SIT 820 control valve operation provided in this manual. Contact a local authorized dealer or Country Flame direct to resolve any issues with specifications or the requirements thereof.
TABLE 3: INGLENOOK LOG SET SPECIFICATIONS
DESCRIPTION | NATURAL GAS | PROPANE GAS |
INPUT RATING (Btu/hr) 0 - 610 Meters* | 65,000 | 65,000 |
MIN INPUT RATING (Btu/hr) 0 – 610 Meters | 42,600 | 43,000 |
ORIFICE SIZE (DMS) 0 – 610 Meters front/rear | 31/43 | 48/55 |
MINIMUM SHUTTER SETTING (inches) | 0 | 1/8 |
PILOT ORIFICE (DMS) | 51 | 35 |
|
|
|
INPUT RATING (Btu/hr) 610 – 1370 Meters | 59,000 | 58,700 |
ORIFICE SIZE (DMS) 610 – 1370 Meters | 32/44 | 49/56 |
|
|
|
MANIFOLD PRESSURE (Inches of Water Column) | 3.5 | 10.0 |
MANIFOLD PRESSURE, Low Setting (Inches of W.C.) | 1.4 | 4.2 |
MINIMUM INLET PRESSURE (Inches of W.C.) | 4.5 | 11.0 |
MAXIMUM INLET PRESSURE (Inches of W.C.) | 7.0 | 14.0 |
*ANSI standards are SAFETY STANDARDS not PERFORMANCE STANDARDS. Performance standards are defined as efficiency standards, A.F.U.E ratings, and efficiency test protocol that is established by the United States Department of Energy.
SHUTTER SETTING
Verify that the adjustable burner air shutter is set according to TABLE 3. FIGURE 4 shows the rear burner assembly (Item B) and the adjustable burner air shutter (Item A). Loosen the locking screw that holds the air shutter in place. Use a proper sized drill bit shank to set the correct opening of the air shutter. Retighten the locking screw. To set the burner air shutter for the front burner assembly, repeat the process.
FIGURE 4: ADJUSTABLE BURNER AIR SHUTTER