
TROUBLESHOOTING INSTRUCTIONS
PROBLEM | POSSIBLE CAUSE | SOLUTION |
Pilot will not | Air in gas lines | Refer to Item #1 of the |
light. | Defective spill switch. | Check for continuity across spill switch leads. Replace spill switch if |
|
| excessive resistance is present or if circuit is electrically open. |
| Wrong Inlet Pressure. | Refer to Item #2 of the |
| Defective piezo spark | Replace electrode if the insulator is cracked or the tip is corroded. Verify that |
| electrode. | the spark gap between the pilot and the electrode is correct. |
| Defective piezo wire. | Replace piezoelectric igniter if its wire insulation is damaged or the wire is |
|
| broken or corroded. |
| Safety interlock function | Allow the thermocouple to cool until the mV drops below the |
| engaged. | requirements of the safety magnet, (30 seconds or less). |
Pilot will not | Wrong inlet pressure | Refer to Item #2 of the |
hold. | Pilot adjustment screw not | Refer to Item #7 in the |
| adjusted properly. |
|
| Thermocouple or thermopile | Refer to Item #3 in the |
| not properly inserted into |
|
| the pilot housing. |
|
| Thermocouple or thermopile | With the thermocouple and thermopile tips cool, clean the upper 3/8” with a |
| has film | very fine emery cloth. |
| Electrical resistance too | Using a very fine emery cloth, clean thermopile and thermocouple |
| high. | connections at valve. Tighten thermocouple into valve hand tight, plus ¼ turn |
|
| with a wrench. |
| Defective thermocouple. | Verify that thermocouple is not kinked or damaged. Check open circuit |
| (mV Plus systems) | voltage of thermocouple. Voltage should be between 18mV and 28mv. If |
|
| voltage is less than 14mV, replace thermocouple. |
| Defective thermopile. | Refer to Item #7 in the |
| (Millivolt system) |
|
| Defective safety magnet. | Verify operation of safety magnet in the following manner. |
| (mV Plus systems) | Depress and hold pilot button. |
|
| Verify |
|
| Reconnect thermocouple to valve. |
|
| Measure the voltage between the solder button on the base of the safety |
|
| magnet, and the valve body. If the mV reading is above 6mV for vented |
|
| appliances, or 8.5mV for |
|
| hold, replace the valve. |
|
| If closed circuit mV reading is the same as the open circuit reading, the coil is |
|
| electrically open. Replace the valve. |
| Defective Safety Magnet | Verify operation of safety magnet in the following manner. |
| (Millivolt system) | Remove all wires from the terminals of the main operator. |
|
| Measure the electrical voltage between the terminals TPTH and TP. If the |
|
| voltage is above 110mV and the safety magnet does not hold, replace the |
|
| valve. |
| Pilot orifice blocked. | Replace orifice with a new orifice of the exact size and type. |
Pilot light | Wrong pilot orifice installed | Replace the orifice with a new orifice supplied specifically for the appliance |
drops out. | in pilot light. | and gas type in question. |
| Spill switch activated. | Examine the venting system. Repair as necessary. |
|
|
|
Version 1.0b | 28 |