Craftsman 919.167362 owner manual Extension Cords, Voltage and Circuit Protection

Models: 919.167362

1 48
Download 48 pages 30.28 Kb
Page 11
Image 11

Extension Cords

Using extension cords is not recommended. The use of extension cords will cause voltage to drop resulting in power loss to the motor and overheating.

Instead of using extension cords attach extra air hoses to each other starting at the air outlet.

If an extension cord must be used, be sure it is:

a 3-wire extension cord that has a 3-blade grounding plug, and a 3-slot receptacle that will accept the plug on the product

in good condition

no longer than 50 feet

12 gauge (AWG) or larger. (Wire size increases as gauge number decreases. 10 AWG and 8 AWG may also be used. DO NOT USE 14 OR 16 AWG.)

Voltage and Circuit Protection

Refer to the Parts Manual for the voltage and minimum branch circuit requirements.

Certain air compressors can be operated on a 15 amp circuit if the following conditions are met.

1.Voltage supply through branch circuit is 15 amps.

2.Circuit is not used to supply any other electrical needs (lights, appliances, etc.).

3.Extension cords comply with specifications.

4.Circuit is equipped with a

15 amp circuit breaker or 15 amp time delay fuse. NOTE: If compressor is connected to a circuit protected by fuses, use only time delay fuses. Time delay fuses should be marked "D" in Canada and "T" in the US.

If any of the above conditions cannot be met, or if operation of the compressor repeatedly causes interruption of the power, it may be necessary to operate it from a 20 amp circuit. It is not necessary to change the cord set.

11- ENG

D28409

Page 11
Image 11
Craftsman 919.167362 owner manual Extension Cords, Voltage and Circuit Protection