WARRANTY NOTE: Both the temperature sensor and moisture detection system must be connected to the motor circuitry such that the motor will be
C-4.4) Overload Protection:
The normally closed (N/C) thermal sensor is embedded in the motor windings and will detect excessive heat in the event an overload condition occurs which will then trip and stop the pump. The thermal sensor leads marked P1 and P2 MUST be connected in series with the stop button of the pilot circuit of the magnetic motor controller located in the control panel so that the thermostat will open the circuit before dangerous temperatures are reached. A manual momentary start switch is required to prevent the automatic restarting of the motor when the thermostat resets. For a typical wiring diagram, refer to Fig. 2. In the event of an overload, the source of this condition should be determined and rectified before the pump is put back into normal operation. DO NOT LET THE PUMP
CYCLE OR RUN IF AN OVERLOAD CONDITION OCCURS!
If current through the temperature sensor exceeds the values listed, an intermediate control circuit relay must be used to reduce the current or the sensor will not work properly.
TEMPERATURE SENSOR ELECTRICAL RATING
VOLTS | CONTINUOUS | INRUSH |
| AMPERES | AMPERES |
3.00 | 30.0 | |
1.50 | 15.0 | |
0.75 | 7.5 |
A normally open (N/O) detector is installed in the pump seal chamber, which will detect any moisture present, and a continuity test resistor built into the motor. The test resistor is rated 1 watt at 330K ohms. The moisture sensors MUST be connected to moisture detector control, which includes a continuity test circuit, see Fig. 3 for typical wiring diagram. The normally closed (N/C) contact of the moisture detector MUST be connected in series with the stop button of the pilot circuit of the magnetic motor controller. A Warrick moisture detection control, Type 2800 is an acceptable control if properly installed and maintained. Wiring must be provided from the moisture detector sensor probe leads of the motor designated W1 and W2 to terminals 9 and 10 of the
OCCURRED, SCHEDULE MAINTENANCE AS SOON AS POSSIBLE!
The control panel and the electrical system MUST be properly designed and wired to include at least, but not limited to the following;
a. Proper grounding per NEC.
b. A temperature sensing circuit (see Fig. 2A & B) c. A moisture detection circuit with continuity test
circuit (see Fig. 3)
d. An intrinsically safe level control system.
e. A main power manual disconnect and lock out.
f.A motor starter and overload system.
g.Single phase only, requires a capacitor power pack (see Fig. 2B).
Control panels for single phase pumps MUST be purchased from the factory and it is advisable that all three phase control panels are also purchased from the factory.
SECTION: D
Before operating pump, compare the voltage and phase information stamped on the pump’s identification plate to the available power.
Before putting pump into service for the first time, the motor rotation must be checked. Improper motor rotation can result in poor pump performance and can damage the motor and/or pump. To check the rotation, suspend the pump freely, momentarily apply power and observe the “kickback”. “Kickback” should always be in a
In the event that the rotation is incorrect for a
Included at the end of this manual are two
Record the numbers from the pump’s identification plate on both
8