B.Trouble shooting problems where a soft lockout code is displayed. When a soft lockout occurs, the boiler will shut down and the display will alternate between the number “9” and the letter “b” followed by a two digit service code. The boiler will automatically restart once the condition that caused the lockout is corrected.

Table 14.3: Soft Lockout Codes Displayed

CODE

CONDITION

POSSIBLE CAUSES

 

 

• Blockage in intake or vent system.

 

 

• Vent and/or intake system not constructed in accordance

 

 

with Part VII.

b 08

Pressure switch circuit open.

• Blocked or leaking pressure switch tubing.

 

 

• Heat exchanger or burner blockage.

 

 

• Terminals exposed to high winds.

 

 

• Blockage in condensate trap above vent.

 

 

 

 

 

• Heating load at time of error was far below the minimum

 

 

firing rate of the boiler.

b 18

MCBA supply sensor detected temperatures in excess

• Defective primary pump or no flow in primary loop (Piping

of 200°F.

Method 1).

 

 

 

• Control system miswired so that boiler operation is

 

 

permitted when no zones are calling.

 

 

 

b 19

MCBA return sensor detected temperatures in excess of

• See possible causes for “b18”.

200°F.

• Flow through boiler reversed.

 

 

 

• Sensor wiring reversed.

 

 

 

 

 

• Flow through boiler reversed. Verify correct piping and

 

MCBA is reading a return sensor temperature higher

pump orientation.

 

• No boiler water flow. Verify that system is purged of air

b 24

than the supply sensor temperature. Condition must be

and that appropriate valves are open.

 

present for at least 75s for this error code to appear.

 

• Sensor wiring reversed.

 

 

 

 

• Supply or return sensor defective.

 

 

 

 

 

• See possible causes for “b18”.

b 25

Supply water temperature has risen too quickly.

• Inadequate boiler water flow. Verify that pump is

operating and that pump and piping are sized per Part IX

 

 

 

 

of this manual.

 

 

 

b 26

Boiler safety limit, or external limit wired across terminals

• See possible causes for “b18”.

3&4, is open.

• Defective supply sensor.

 

 

 

 

 

 

• Inadequate boiler water flow. Verify that pump is

b 30

Temperature rise between supply and return is too high.

operating and that pump and piping are sized per Part IX

 

 

of this manual.

 

 

• Blockage in pressure switch hose.

 

 

• Pressure switch wires shorted together.

b 61

Pressure switch circuit closed with fan off.

• Defective pressure switch.

 

 

• Loose or miswired fan speed harness (if “b61” error code

 

 

is observed while fan is running).

 

 

 

b 65

Fan is not achieving set point speed.

• Loose or incorrect fan speed control connection.

• Defective fan.

 

 

 

 

 

71

Page 73
Image 73
Crown Boiler BWC151 manual Soft Lockout Codes Displayed