8)Flow control valve (Required under some conditions) – The flow control valve prevents flow through the system unless the circulator is operating. A flow control valve may be necessary on converted gravity systems to prevent gravity circulation. Flow control valves are also used to prevent “ghost flows” in circulator zone systems through zones that are not calling for heat.

9)Isolation Valves (Optional) – Isolation valves are useful if the boiler must be drained, as they will eliminate having to drain and refill the entire system.

10)Drain Valve – The drain valve is shipped in the boiler parts bag. Install it in the location shown in Figure 1.

B. Piping for Special Situations

Certain types of heating systems have additional requirements. Some of the more common variations follow:

1)Indirect Water Heaters – Figure 27 shows typical indirect water heater piping. Boiler piping is the same as for any two-zone system. Figure 27 shows circulator zoning, which is usually preferred for indirect water heaters. Size the circulator and indirect water heater piping to obtain the boiler water flow through the indirect water heater called for by the indirect water heater manufacturer. The standard CWD control system will operate two circulator zones. See the Wiring section of this manual.

2)Gravity and “Large Water Volume” Systems – The piping shown in Figure 28 will minimize the amount of time that the boiler operates with return temperatures below 120F on these systems. A bypass is installed as shown to divert some supply water directly into the return water. The bypass pipe should be the same size as the supply. The two throttling valves shown are adjusted so that the return temperature rises above 120F during the first few minutes of operation. A three-way valve can be substituted for the two throttling valves shown. If the circulator is mounted on the supply, the bypass must be on the discharge side of the circulator.

3)Low Temperature Systems – Some systems, such as radiant tubing systems, require the system water temperature to

be limited to a value below the temperature of the water leaving the CWD. These systems also typically have return temperatures well below the 120F minimum.

Figure 29 illustrates the use of a heat exchanger to connect a CWD boiler to this type of system. The heat exchanger will permit the transfer of heat from the boiler water to the low temperature system while holding the system supply and boiler return temperatures within their limits. For this system to work properly, the heat exchanger must be properly sized and the correct flow rates are required on either side of the heat exchanger. Consult the heat exchanger manufacturer for sizing information. The water in the boiler is completely isolated from the water in the system. This means that separate fill and expansion tanks are required for the heating system loop.

There are several other ways to connect low temperature systems to the non-condensing boilers like the CWD such as four way mixing valve and variable speed injection pumping systems.

4)Systems containing oxygen – Many hydronic systems contain enough dissolved oxygen to cause severe corrosion damage to a cast iron boiler such as the CWD. Some examples include:

Radiant systems that employ tubing without an oxygen barrier.

Systems with routine additions of fresh water.

Systems which are open to the atmosphere.

If the boiler is to be used in such a system, it must be separated from the oxygenated water being heated with a heat exchanger as shown in Figure 29.

Consult the heat exchanger manufacturer for proper heat exchanger sizing as well as flow and temperature requirements. All components on the oxygenated side of the heat exchanger, such as the pump and expansion tank, must be designed for use in oxygenated water.

5)Piping with a Chiller – If the boiler is used in conjunction with a chiller, pipe the boiler and chiller in parallel as shown in Figure 30. Use isolation valves to prevent chilled water from entering the boiler.

6)Air Handlers – Where the boiler is connected to air handlers through which refrigerated air passes, use flow control valves in the boiler piping or other automatic means to prevent gravity circulation during the cooling cycle.

34

Page 36
Image 36
Crown Boiler CWD138, CWD083, CWD220, CWD060, CWD165, CWD193, CWD245, CWD110 Piping for Special Situations

CWD193, CWD165, CWD245, CWD220, CWD110 specifications

Crown Boiler Company is well-known for its commitment to quality and performance in the heating industry. Among its extensive range of products, the Crown Boiler CWD series stands out for its reliability and efficiency. This series includes models CWD060, CWD083, CWD110, CWD138, and CWD220, each designed to meet diverse heating needs in residential and commercial applications.

One of the main features of the CWD series is its durable construction. Made with high-quality materials, these boilers are built to withstand the test of time. The cast iron heat exchanger delivers exceptional heat retention and efficiency, ensuring optimal performance even in demanding conditions. Additionally, the CWD models are equipped with a reliable standing pilot ignition system, which enhances user safety and operational reliability.

Another important characteristic of the Crown CWD series is its versatility in fuel options. These boilers can operate on either natural gas or propane, providing flexibility to homeowners and businesses depending on their preferred energy source. The ability to easily switch fuels makes these units adaptable to various heating applications, maximizing convenience for users.

Efficiency is a cornerstone of the Crown Boiler CWD series. With an AFUE rating of up to 85%, these boilers deliver substantial cost savings over the heating season. Their efficient operation not only lowers energy bills but also contributes to a reduced environmental impact, which is increasingly important in today’s energy-conscious world.

Crown’s innovative design features also include a low water cut-off and a built-in draft hood. The low water cut-off ensures safe operation by preventing the boiler from running dry, while the draft hood allows for optimal venting capabilities, minimizing the risk of dangerous flue gas build-up.

Maintenance is straightforward with the CWD series, thanks to its easy-access design. Routine service and inspections can be performed with minimal disruption, ensuring that the units maintain peak performance over their lifespan.

The Crown Boiler CWD060, CWD083, CWD110, CWD138, and CWD220 models exemplify the brand’s dedication to delivering high-quality heating solutions. With their impressive efficiency ratings, durable construction, versatile fuel options, and user-friendly features, these boilers represent a smart investment for anyone looking to enhance heating reliability and comfort in their space.