BATTERY REPLACEMENT AND STORAGE

Contact your dealer or call the number in this manual for information on battery replacement.

Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of personnel knowledgeable of batteries and their precautions. Keep unauthorized personnel away from batteries.

CAUTION! Use only the specified type of battery. See your dealer for replacement batteries. CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a fire, as it may explode. Follow all local ordinances regarding proper disposal of batteries.

CAUTION! Do not open or mutilate the batteries. Release electrolyte is harmful to the skin and eyes and may be toxic.

CAUTION! A battery can present a high risk of short circuit current and electric shock. Take the following precautions before replacing the battery:

1.Remove all watches, rings or other metal objects.

2.Only use tools with insulated handles.

3.DO NOT lay tools or other metal parts on top of battery or any battery terminals.

4.Wear rubber gloves and boots.

5.Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of

ground. CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit).

BATTERY REPLACEMENT PROCEDURE:

1.Turn off and unplug all connected equipments.

2.Turn the UPS off and unplug it from the AC power source.

3.Carefully turn the UPS upside down. Remove the 6 retaining screws and the cover.

4.Disconnect the black and red wires from the battery set.

5.Remove the battery protection cover and take out the battery set from the compartment.

6.Slide a new battery pack into the unit. Assemble the battery protection cover, cable, screws in the reverse sequence of above steps.

REMINDER: Recharge the unit for 4 – 8 hours to ensure the UPS performs expected runtime

STORAGE:

First turn off your UPS and disconnect its power

cord from the wall outlet. Disconnect all cables connected to the UPS to avoid battery drain. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to insure battery life. If the battery remains uncharged for an extended period of time, it may suffer permanent loss of capacity.

TROUBLE SHOOTING

Problem

Possible Cause

Solution

The UPS does not

Batteries are not fully

Recharge the battery by leaving the UPS

charged.

plugged in.

perform expected

 

Contact CyberPower Systems at

runtime.

Battery is slightly worn out.

service@cyberpower-eu.com

 

 

 

The on/off switch is

 

 

designed to prevent

Turn the UPS off. Wait 10 seconds and then

 

damage by rapidly turning it

turn the UPS on.

The UPS will not

off and on.

 

The unit is not connected to

The unit must be connected to a 220-240V

turn on.

an AC outlet.

50/60Hz outlet.

 

 

The battery is worn out.

Contact CyberPower Systems at

 

service@cyberpower-eu.com

 

 

 

Mechanical problem.

Contact CyberPower Systems at

 

service@cyberpower-eu.com

 

 

 

 

Turn the UPS off and unplug at least one

 

Circuit breaker is tripped due

piece of equipment. Wait 10 seconds, reset

Outlets do not

to overload

the circuit breaker and then turn the UPS on.

 

 

 

Allow the unit to recharge for at least 4

provide power to

Batteries are discharged

equipment

hours.

 

 

 

 

 

Unit has been damaged by

Contact CyberPower Systems at

 

a surge or spike.

service@cyberpower-eu.com

 

 

 

 

The serial/USB cable is not

Connect the serial/USB cable to the UPS

 

unit and an open serial port on the back of

 

connected.

the computer. You must use the cable that

 

 

came with the unit.

PowerPanel®

The serial/USB cable is

Try another serial/USB port of your

Business Edition is

connected to the wrong

computer.

port.

inactive (all icons

 

 

Shutdown your computer and turn the UPS

are gray).

The unit is not providing

off. Wait 10 seconds and turn the UPS back

 

battery power.

 

on. This should reset the unit.

 

 

 

The serial cable is not the

You must use the cable included with the

 

cable that was provided with

 

unit for the software.

 

the unit.

 

 

TECHNICAL SPECIFICATIONS

Model

 

 

 

 

 

 

PP1500E

 

PP2200E

 

Capacity

(VA)

 

 

 

 

1500VA

 

2200VA

 

Capacity

(Watts)

 

 

 

 

1000W

 

 

1600W

 

Input

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage Range

 

 

 

 

 

220-240Vac

 

Frequency Range

 

 

 

 

 

 

 

50/60 Hz

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

On Battery Output Voltage

 

 

Pure Sine Wave at 230Vac +/- 7%

 

On Battery Output Frequency

 

 

 

 

 

50/60 Hz

 

Overload Protection

 

 

 

On Utility: Circuit Breaker, On Battery: Internal Current Limiting

 

Surge Protection and Filtering

 

 

 

 

 

 

 

 

Lightning / Surge Protection

 

 

 

 

 

Yes

 

Network Protection

 

 

 

 

 

 

RJ45 (One In/One Out)

 

Physical

 

 

 

 

 

 

 

 

 

 

 

 

Total # of UPS Receptacles

 

 

 

 

(8) IEC 320 C13

 

Maximum Dimensions

 

 

 

 

42.0cm*18.0cm*23.7cm

 

Weight (Kg)

 

 

 

 

25.4

 

 

31.1

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

Sealed Maintenance Free

 

 

12V / 7AHx4

 

12V / 9AHx4

 

Lead Acid Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Replaceable

 

 

 

 

Yes, Hot Swappable Battery Pack

 

Typical Recharge Time

 

 

 

 

 

8 Hours

 

Warning Diagnostics

 

 

 

 

 

 

 

 

Indicators

 

 

 

 

 

Power On, Using Battery, AVR, Load Level, Battery Level

 

Audible Alarms

 

 

 

 

On Battery, Low Battery, Overload

 

Environmental

 

 

 

 

 

 

 

 

 

 

Operating Temperature

 

 

 

+32°F to 95°F ( 0°C to 35°C )

 

Operating Relative Humidity

 

 

 

0 to 95% NON-CONDENSING

 

Communication

 

 

 

 

 

 

 

 

 

 

PowerPanel® Business

 

 

Windows 98/ME/2000/NT/XP, Server 2003

 

Edition Software

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Management

 

 

 

 

 

 

 

 

 

 

Auto-Charger

 

 

 

 

 

 

 

Yes

 

Auto-Restart

 

 

 

 

 

 

 

Yes

 

USB Interface

 

 

 

 

 

 

 

Yes

 

SNMP/HTTP Network

 

 

 

 

 

Optional

 

 

 

DEFINITIONS FOR ILLUMINATED LED INDICATORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using

 

Circuit

 

 

 

 

Condition

Power

 

AVR

 

 

Alarm

 

 

 

 

 

 

 

Battery

 

Breaker

 

 

 

 

 

On

 

 

 

 

 

 

 

 

 

 

 

 

 

On

 

Off

 

Off

 

 

Set

Off

 

 

 

Normal

On

 

Slow

 

Off

 

 

Set

Off

 

AVR- Max. boost 13% of input voltage for output

 

 

 

 

 

regulation while input voltage is from 5% to 14%

 

flash

 

 

 

 

 

 

 

 

 

 

 

 

 

under nominal.

 

 

 

 

 

 

 

 

 

 

On

 

Rapid

 

Off

 

 

Set

Off

 

AVR- Max. boost 26% of input voltage for output

 

 

 

 

 

regulation while input voltage is from 15% to 26%

 

flash

 

 

 

 

 

 

 

 

 

 

 

 

 

under nominal.

 

 

 

 

 

 

 

 

 

 

ON

 

On

 

Off

 

 

Set

Off

 

AVR- Max. buck 10% of input voltage for output

 

 

 

 

 

regulation while input voltage is from 7% to 22%

 

 

 

 

 

 

 

 

 

 

over nominal.

Off

 

Off

 

On

 

 

Set

Two

 

Utility Failure- The UPS is providing battery

 

 

 

 

Beeps

 

power to the Battery-Power Supplied outlets.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rapid

 

Utility Failure- The UPS is providing battery

Off

 

Off

 

On

 

 

Set

 

power.

Rapid beeps indicate the battery will run

 

 

 

 

Beeps

 

 

 

 

 

 

 

 

 

 

out of charge within a few minutes.

 

 

 

 

 

 

 

 

 

 

 

 

On/ Off

 

 

 

 

 

Long

 

Overload- Turn the UPS off and unplug at least

On/Off

 

 

On/Off

 

 

Set

 

one piece of equipment from the UPS. Wait 5

 

/Flash

 

 

 

Beep

 

seconds, reset the circuit breaker and restart the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS.

 

 

 

 

 

 

 

 

 

 

 

Long

 

Overload- Turn the UPS off and unplug at least

Off

 

Off

 

On

 

 

Up

 

one piece of equipment from the UPS. Wait 5

 

 

 

 

Beep

 

seconds, reset the circuit breaker and restart the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS.

 

 

 

Off

 

Off

 

Off

 

 

Set

Off

 

Surge Protection Malfunction- Power surge has

 

 

 

 

 

damaged the unit. Please contact CyberPower

 

 

 

 

 

 

 

 

 

 

Systems.

For more information, visit eu.cyberpowersystems.com or contact

CyberPower Systems B.V. Flight Forum 3545, 5657DW Eindhoven, The Netherlands Tel: +31 (0)40 2348170, E-MAIL: sales@cyberpower-eu.com

CyberPower Systems Inc. (USA) 4241 12th Avenue East Suite 400 Shakopee, MN 55379, U.S.A. Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: sales@cyberpowersystems.com

Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel® and PowerPanel® Plus are trademarks of CyberPower Systems (USA) Inc.

CyberPower warrants to you, the original purchaser, that CyberPower UPS will be free from defects in design, assembly, materials and workmanship for two years ( battery is only one year) from the date of original purchase. Any warranty services, please contact your local dealers or distributors

Page 2
Image 2
CyberPower Systems PP1500E, PP2200E user manual Battery Replacement and Storage, Trouble Shooting, Technical Specifications