DeLonghi WIR1, WIR2 manual Equipment Shutoff Valve, Checking Gas Joints for Natural Gas

Models: WIR2 WIR1

1 19
Download 19 pages 34.58 Kb
Page 10
Image 10
Fig.8 Equipment Shutoff Valve

WIR 2 26-06-2003 18:21 Pagina 10

Test pressures equal or less than 1/2 PSIG (3,5 Kpa)

1.Close equipment shutoff valve (see figure 8).

2.Pressurize supply piping system by either opening propane/LP supply tank valve located on or near gas meter for natural gas, or using compressed air.

3.Check all joints from gas meter for natural gas (see figure B) or propane/LP supply tank for propane /LP gas, to equipment shutoff valve (see figure C). Apply a non- corrosive leak detection fluid to all joints. Bubbles forming show a leak.

4.Correct all leaks at once.

PRESSURE TESTING HEATER GAS CONNEC- TIONS

1.Open equipment shutoff valve (see figure A).

2.For natural gas open main gas valve locat- ed on or near gas meter. For propane/LP gas open propane /LP supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve thermostat gas valve (see figure 8/9 or 10). Apply a non-corrosive leak detection fluid to all joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Light heater (see operating heater, page 11). Check all other internal joints for leaks.

7.Turn off heater (see to turn off gas to appli- ance, page 12)

Fig.8 Equipment Shutoff Valve

Fig.9 Checking Gas Joints for Natural Gas

Fig.10 Checking Gas Joints for Propane/LP Gas