Denso 36 Technical Specifications, Item/Features, Office Pro, Specifications, Cooling Unit, Blower

Models: 36

1 16
Download 16 pages 60.4 Kb
Page 14
Image 14
TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS

ITEM/FEATURES

 

OFFICE PRO 36

Rating Conditions

 

 

dry bulb

 

95º F (35º C)

wet bulb

 

83º F (28.2º C)

humidity

 

60%

Specifications

 

 

power frequency

 

60Hz

line voltage

 

single phase 208/230V

power consumption

4.4 Kw

current consumption

19.7 Amps

power factor

 

99%

starting current

 

88A

power wiring

 

10 (3-core) AWG

Cooling Unit

 

 

cooling capability

 

9,070 Kcal/hr

 

 

36,000 BTU/hr

cooling system

 

direct expansion

Blower

 

 

type of fan

 

centrifugal fan

air volume:

evaporator (high speed)

999 ft 3/min (1682 m3/h)

 

evaporator (low speed)

825 ft 3/min (1402 m3/h)

 

condenser (high speed)

1490 ft3/min (2532 m3/h)

 

evaporator (low speed)

1060 ft3/min (1801 m3/h)

motor output:

evaporator (high)

0.21 Kw

 

condenser (high)

0.33 Kw

Compressor

 

 

type

 

hermetic scroll

output

 

2.1 Kw

refrigerant type

 

R-22

refrigerant capacity

2.4 lbs (3.1 kg)

Safety Devices

 

 

compressor overload protector

included

fan motor protector

included

anti-freezing thermistor

included

full drain tank switch

included

automatic restart (power interruption)

included

compressor time delay program

included

Dimensions & Weight

 

W x D x H (in)

 

30” x 44” x 52”

W x D x H (mm)

 

760 x 1117.6 x 1321

weight (lbs/kg)

 

540/245

Operating Conditions

 

inlet air (relative humidity)

95º F (35º C), 60%

 

 

65º F (18.3º C), 50%

Control Device

 

 

temperature control

included

programmable timer

included

two speed fan

 

included

11