6
INSTALLATION
Venting Installation Precautions Venting Installation
INSTALLATION
WARNING: Read all instructions completely and thoroughly before attempting installation. Failure to do so could result in serious injury, property damage or loss of life. Operation of improperly installed and maintained venting system could result in serious injury, property damage or loss of life.
NOTICE: Failure to follow these instructions will void the warranty.
VENTING INSTALLATION PRECAUTIONS
Consult local building codes before beginning the installation. The installer must make sure to select the proper vent system for installa- tion. Before installing vent kit, the installer must read this fireplace manual and vent kit instructions.
Only a qualified service person should install venting system. The installer must follow these safety rules:
•Wear gloves and safety glasses for protection
•Use extreme caution when using ladders or when on roof tops
•Be aware of electrical wiring locations in walls and ceilings
The following actions will void the warranty on your venting system:
•Installation of any damaged venting component
•Unauthorized modification of the venting system
•Installation of any component part not manufactured or approved by DESA
•Installation other than as instructed by these instructions
3.When installation of vent pipe is complete, in stall vent termi- nation. Depending on the location of your fireplace, you will vent vertically or horizontally.
4.Allow 1" of pipe to protrude from internal wall, depending on wall thickness. See Figure 7.
5.For horizontal installation, an optional siding standoff may be installed between the vent cap and the exterior wall. Secure horizontal vent cap to standoff. Secure standoff/vent cap as- sembly to wall (see Figure 7). Do not seal termination to vent pipe. The vent termination must be removable for service pipe inspection.
6.For vertical installation, a vertical termination is available. Also for vertical venting application, install vertical flue restrictor into inner collar of fireplace as shown in Figure 6.
When installing a length of pipe for vertical termination that is over 3 ft., support the pipe every 3 ft. using metal wall straps. Vertical to horizontal pipe must be kept at a 1 ft. to 4 ft. ratio with a maximum run of no more than 20 ft.
Female Locking Lugs | Male Locking |
Lugs |
Vertical Flue Restrictor
(For Vertical Venting
Application)
WARNING: This gas fireplace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serv- ing a separate solid fuel burning appliance. Each gas appliance must use a separate vent system. Do not use common vent systems.
WARNING: Horizontal sections of this vent sys- tem require a minimum clearance of 2" from the top of the pipe and 1" minimum to the sides and bottom. Vertical sections of this system require a minimum of 1" clearance to combustible materials on all sides of the pipe.
VENTING INSTALLATION
1.Install elbow to fireplace collar adapter located on back of the unit at a 45° angle. Slide elbow over collar and twist to lock. Check to insure proper connection (see Figure 6).
2.Continue to install remainder of pipe for desired installation. Make sure each section is
Figure 6 - Venting Installation
CD32M and
4 1/4" Inner and 7 1/4" Outer
5" Inner and 8" Outer
Wall
Firestop
Maintain 1" Minimum Air Space Around Outer Pipe when Penetrating a Wall
Framed Openings
CD32M and
10" x 10"
10 3/4" x 10 3/4"
Siding Standoff (Optional)
Minimum Pipe
Overlap 1 1/4"
Deflector Shield
Screws
Horizontal
Termination
(Vent Cap)
Exterior Wall with
Vinyl Siding
Figure 7 - Vent Termination (Horizontal)
For..com