Desa CDR3924PT installation manual Checking GAS Connections, Propane/LP From, Natural From Gas

Models: CDR3924PT

1 28
Download 28 pages 28.92 Kb
Page 13
Image 13

INSTALLATION

Continued

We recommend that you install a sediment trap in supply line as shown in Figure 13. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings.

Propane/LP - From

CSA Design-

External Regulator

(11" W.C.** to 14" W.C.

Certified Equipment

Pressure)

 

Shutoff Valve With

Natural - From Gas

1/8" NPT Tap*

Meter

 

 

(5" W.C.** to

Approved Flexible

10.5" W.C.

 

 

Gas Hose (if allowed

Pressure)

 

 

by local codes)

 

 

 

3"

 

 

Minimum

Tee Cap

Pipe

Gas

Joint

Nipple

Regulator

Sediment Trap

Figure 13 - Gas Connection

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 25.

**Minimum inlet pressure for purpose of input adjustment.

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip- ing and connections, internal and external to unit, for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater. See guidelines un- der Connecting to Gas Supply, page 12.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

4.Check all joints of gas supply piping system. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

113183-01A

www.desatech.com

13

Page 13
Image 13
Desa CDR3924PT Checking GAS Connections, Propane/LP From, Natural From Gas, Test Pressures In Excess Of 1/2 Psig 3.5 kPa