TROUBLESHOOTING

Continued

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

 

 

 

 

ODS/pilot lights but flame

1. Control knob not fully pressed in

1.

Press in control knob fully

goes out when control knob is

2. Control knob not pressed in

2.

After ODS/pilot lights, keep con-

released

 

long enough

 

trol knob pressed in 30 seconds

 

3.

Equipment shutoff valve not

3.

Fully open equipment shutoff

 

 

fully open

 

valve

 

4.

Pilot flame not touching ther-

4.

A) Contact local natural or

 

 

mocouple, which allows ther-

 

propane/LP gas company

 

 

mocouple to cool, causing

 

B) Clean ODS/pilot (see

 

 

pilot flame to go out. This

 

 

 

problem could be caused by

 

Cleaning and Maintenance,

 

 

one or both of the following:

 

page 21) or replace ODS/pilot

 

 

A) Low gas pressure

 

assembly

 

 

B) Dirty or partially clogged

 

 

 

 

ODS/pilot

 

 

 

5.

Thermocouple connection

5.

Hand tighten until snug, then

 

 

loose at control valve

 

tighten 1/4 turn more

 

6.

Thermocouple damaged

6.

Replace pilot assembly

 

7.

Control valve damaged

7.

Replace control valve

 

 

 

 

Burner does not light after

1. Inlet gas pressure is too low

1.

Contact local natural or pro-

ODS/pilot is lit

2.

Burner orifice(s) clogged

 

pane/LP gas company

 

2.

Clean burner(s) (see Cleaning

 

 

 

 

and Maintenance, page 21) or

 

 

 

 

replace burner orifice

 

 

 

 

Delayed ignition of burner

1. Manifold pressure is too low

1.

Contact local natural or pro-

 

2.

Burner orifice(s) clogged

 

pane/LP gas company

 

2.

Clean burner(s) (see Cleaning

 

 

 

 

and Maintenance, page 21) or

 

 

 

 

replace burner orifice

 

 

 

 

Burner backfiring during com-

1. Burner orifice is clogged or

1.

Clean burner (see Cleaning

bustion

 

damaged

 

and Maintenance, page 21)

 

 

 

 

or replace burner orifice

 

2.

Damaged burner

2.

Replace damaged burner

 

3.

Gas regulator defective

3.

Replace gas control

 

 

 

 

Slight smoke or odor during

1. Not enough air

1.

Check burner for dirt and

initial operation

 

 

 

debris. If found, clean burner

 

 

 

 

(see Cleaning and Mainte-

 

2.

Gas regulator defective

 

nance, page 21)

 

2.

Replace gas control

 

3.

Residues from manufacturing

3.

Problem will stop after a few

 

 

processes and logs curing

 

hours of operation

24

www.desatech.com