Pressure Testing Heater Gas Connections

DESA INTERNATIONAL

UNVENTED NATURAL GAS LOG HEATER

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

Pressure Testing gas Supply Piping system WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

Manual background WARNING: Never use an open

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Fig- ure 14).

2.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to manual shutoff valve (see Figure 15). Apply mix- ture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Pressure Testing Heater Gas Connections

1.

Open manual shutoff valve (see Fig-

 

ure 14).

2.

Open main gas valve located on or near

 

gas meter.

3.

Make sure control knob of heater is in

 

the OFF position.

4.

Check all joints from manual shutoff

 

valve to gas control (see Figure 15). Ap-

 

ply mixture of liquid soap and water to

 

gas joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing gas Supply Piping system

Manual

Shutoff

Valve

Open

Closed

6.

Light heater (see Operating Heater,

 

pages 14 through 16). Check all other

 

internal joints for leaks.

7.

Turn off heater (see To Turn Off Gas to

 

Appliance, page 15).

Test Pressures In Excess Of 1/2 PSIG

1.Disconnect heater and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where manual shutoff valve was connected.

3.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Reconnect heater and manual shutoff valve to gas supply. Check reconnected fittings for leaks.

Figure 14 - Manual Shutoff Valve

Manual Shutoff Valve

Gas Meter

Gas Control Location

Figure 15 - Checking Gas Joints

12

103449