INSTALLING Minimum Non Combustible Material Clearances
Continued
If Using Mantel
You must have non combustible material(s) above the fireplace opening. Non combustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non combustible material behind it. Non combustible material must extend at least 8 inches up (for all models). If non combustible material is less than 12", you must install the fireplace hood acces- sory (24" and 30" models only). Even if non combustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See chart below and Figures 6 and 7 for minimum clearances.
IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open.
Requirements for | |
Material Distance (A) | Safe Installation |
|
|
12" or more | Non combustible material okay. |
Between 8" and 12" | Install fireplace hood accessory (GA6050 or |
| GA6052, see Accessories, page 29). |
Less than 8" | Non combustible material must be extended to at |
| least 8". See Between 8" and 12", above. If you |
| cannot extend material, you must operate heater |
| with flue damper open. |
|
|
Mantel Clearances
If you meet minimum clearance between mantel shelf and top of fireplace open- ing, a hood is not required (see Figure 6).
Mantel Shelf
10"
Underside of
| 8" |
|
|
|
|
| Mantel Shelf | ||
|
|
|
|
|
|
|
| ||
| 6" |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
| 2 1/2" |
|
|
|
|
| All minimum | ||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| distances are |
Minimum Non- |
|
| (A) |
|
|
|
|
| in inches |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
Combustible |
|
|
|
|
|
|
| Log Set | |
|
|
|
|
|
|
|
| ||
Material |
|
|
|
|
|
|
|
| |
|
| 12" | 20" | 241/2" | 271/2" | 30" |
| 24"/30" Models | |
|
|
|
| ||||||
|
|
| 8" | 14" | 163/4" | 181/2" | 20" |
| 18" Model |
|
|
|
| ||||||
|
|
|
|
|
|
|
| Top of Fireplace | |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Opening |
Minimum Non- | Distances to |
Combustible | Underside of |
Material Height | Mantel |
Figure 6 - Minimum Mantel Clearances Without Using Hood
If above minimum clearances are not met, you must have a hood. Follow
minimum clearances shown in Figure 7 when using hood. | Continued 11 |